This Harmony RE17R timing relay can be set between 0.1 seconds and 100 hours, has an output rating of 8A, is 17.5mm wide and can be supplied with 24V DC, 24V to 240V AC. It also has 1 changeover contact SPDT (single pole double throw). It has one of market slimmest form-factors, allowing for a flexible and easy installation on DIN rail, using the same space as any modular 1-pole DIN device. It also offers a sealable cover, simple and precise settings with rotary trimmers. Multi function timer for a simple integration in hard-wired logic schematics, ideal for refurbishment of old installations without using a PLC.
Main
Range of Product: Harmony Timer Relays
Discrete output type: Relay
Product or Component Type: Modular timing relay
Width: 17.5 mm
Device short name: RE17R
Time delay type: Power on-delay
On-delay and off-delay
Interval
Off-delay
Symmetrical flashing
Time delay range: 6…60 min
1…10 h
0.1…1 s
1…10 s
1…10 min
10…100 h
6…60 s
Nominal output current: 8 A
Contacts type and composition: 1 C/O
Contacts material: Cadmium free
Height: 90 mm
Depth: 72 mm
Control type: Selector switch front panel
[Us] rated supply voltage: 24…240 V AC 50/60 Hz
24 V DC
Voltage range: 0.85…1.1 Us
Supply frequency: 50…60 Hz +/- 5 %
Release of input voltage: 10 V
Connections – terminals: Screw terminals, 1 x 0.5…1 x 3.3 mm² 20 AWG…12 AWG) solid without cable end
Screw terminals, 2 x 0.5…2 x 2.5 mm² 20 AWG…14 AWG) solid without cable end
Screw terminals, 1 x 0.2…1 x 2.5 mm² 24 AWG…14 AWG) flexible with cable end
Screw terminals, 2 x 0.2…2 x 1.5 mm² 24 AWG…16 AWG) flexible with cable end
Tightening torque: 5.3…8.9 lbf.in (0.6…1 N.m) IEC 60947-1
Housing material: Polycarbonate
Repeat accuracy: +/- 0.5 % IEC 61812-1
Temperature Drift: +/- 0.05 %/°C
Voltage drift: +/- 0.2 %/V
Setting accuracy of time delay: +/- 10 % of full scale 25 °C IEC 61812-1
Time delay type: Power on-delay – A- Power on-delay relay
On-delay and off-delay – Ac- On-delay and off-delay relay w/ control signal
Power on-delay – At- Power on-delay relay w/ pause/summation (Y1)
Interval – B- Single interval relay w/ control signal
Interval – Bw- Double interval relay w/ control signal
Off-delay – C- Off-delay relay w/ control signal
Symmetrical flashing – D- Symmetrical flashing relay (starting pulse-off)
Symmetrical flashing – Di- Symmetrical flashing relay (starting pulse-on)
Interval – H- Interval relay
Interval – Ht- Interval relay w/ pause/summation (Y1)
Control signal pulse width: 100 ms with load in parallel typical
30 ms typical
Insulation resistance: 100 MOhm 500 V DC IEC 60664-1
Reset time: 120 ms on de-energisation typical
On-load factor: 100 %
Power consumption in VA: 0…32 VA 240 V AC
Maximum power consumption in W: 0.6 W 24 V DC
Minimum switching current: 10 mA 5 V DC
Maximum switching current: 8 A AC/DC
Maximum switching voltage: 250 V AC
Breaking capacity: 2000 VA
Operating frequency: 10 Hz
Electrical durability: 100000 cycles resistive 8 A 250 V AC
Mechanical durability: 10000000 cycles
Dielectric strength: 2.5 kV 1 mA/1 minute 50 Hz IEC 61812-1
[Uimp] rated impulse withstand voltage: 5 kV 1.2/50 µs
Power on delay: 100 ms
Marking: CE
Creepage distance: 4 kV/3 IEC 60664-1
Safety reliability data: B10d = 270000
MTTFd = 296.8 years
Mounting position: Any position in relation to normal vertical mounting plane
Mounting support: 35 mm DIN rail conforming to IEC 60715
Local signalling: LED indicator on steady: relay energised, no timing in progress
LED indicator 80 % ON and 20 % OFF flashing: timing in progress
LED indicator 5 % ON and 95 % OFF pulsing: relay de-energised, no timing in progress (except function Di-D, Li-L)
Function available: A- Power on-delay relay-1 C/O
Ac- On-delay and off-delay relay w/ control signal-1 C/O
At- Power on-delay relay w/ pause/summation (Y1)-1 C/O
B- Single interval relay w/ control signal-1 C/O
Bw- Double interval relay w/ control signal-1 C/O
C- Off-delay relay w/ control signal-1 C/O
D- Symmetrical flashing relay (starting pulse-off)-1 C/O
Di- Symmetrical flashing relay (starting pulse-on)-1 C/O
H- Interval relay-1 C/O
Ht- Interval relay w/ pause/summation (Y1)-1 C/O
Net Weight: 0.07 kg
Control Type: Without test button
Number of functions: 10
Time delay type: A, Ac, At, B, Bw, C, D, Di, H, Ht
Functionality: Multifunction
Compatibility code: RE17
Complementary
Immunity to microbreaks: 20 ms
Standards: 2006/95/EC
2004/108/EC
IEC 61812-1
IEC 61000-6-2
IEC 61000-6-3
IEC 61000-6-4
IEC 61000-6-1
Product Certifications: CSA
GL
cULus
Ambient Air Temperature for Storage: -22…140 °F (-30…60 °C)
Ambient Air Temperature for Operation: -4…140 °F (-20…60 °C)
IP degree of protection: IP20 IEC 60529 terminal block)
IP40 IEC 60529 housing)
IP50 IEC 60529 front panel)
Vibration resistance: 20 m/s² (f= 10…150 Hz) conforming to IEC 60068-2-6
Shock resistance: 15 gn 11 ms IEC 60068-2-27
Relative Humidity: 93 % without condensation IEC 60068-2-30
Electromagnetic compatibility: Electrostatic discharge immunity test 6 kV in contact) level 3 IEC 61000-4-2
Electrostatic discharge immunity test 8 kV in air) level 3 IEC 61000-4-2
Susceptibility to electromagnetic fields 10 V/m 80 MHz to 1 GHz) level 3 IEC 61000-4-3
Electrical fast transient/burst immunity test 1 kV capacitive connecting clip) level 3 IEC 61000-4-4
Electrical fast transient/burst immunity test 2 kV direct) level 3 IEC 61000-4-4
1.2/50 µs shock waves immunity test 1 kV differential mode) level 3 IEC 61000-4-5
1.2/50 µs shock waves immunity test 2 kV common mode) level 3 IEC 61000-4-5
Conducted RF disturbances 10 V 0.15…80 MHz) level 3 IEC 61000-4-6
Voltage dips and interruptions immunity test 0 % 1 cycle) IEC 61000-4-11
Voltage dips and interruptions immunity test 70 % 25/30 cycles) IEC 61000-4-11
Conducted and radiated emissionsclass B EN 55022
Environment
Category: US10CP222370
Discount Schedule: 0CP2
Returnability: Yes
Country of origin: ID
Contractual warranty
Warranty: 18 months