Description
General Information
Extended Product Type: S202-K63
Product ID: 2CDS252001R0607
EAN: 4016779551175
Catalog Description: Miniature Circuit Breaker – S200 – 2P – 63 A – K – (AC) 6 kA
Long Description: System pro M compact S200 miniature circuit breakers are current limiting. They have two different tripping mechanisms, the delayed thermal tripping mechanism for overload protection and the electromechanic tripping mechanism for short circuit protection. They are available in different characteristics (B,C,D,K,Z), configurations (1P,1P+N,2P,3P,3P+N,4P), breaking capacities (up to 6 kA at 230/400 V AC) and rated currents (up to 63A). All MCBs of the product range S200 comply with IEC/EN 60898-1, IEC/EN 60947-2, UL1077 allowing the use for residential, commercial and industrial applications. Bottom-fitting auxiliary contact can be mounted on S200 to save 50% space.
Technical
Standards: IEC/EN 60898-1, IEC/EN 60947-2, UL 1077
Number of Poles: 2
Number of Protected Poles: 2
Tripping Characteristic: K
Rated Current (In): 63 A
Rated Operational Voltage: acc. to IEC 60947-2 440 V AC
Operational Voltage: Maximum (Incl. Tolerance) 125 V DC, Maximum (Incl. Tolerance) 440 V AC
Rated Short-Circuit Capacity: (AC) 6 kA, (DC) 6 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu): (125 V DC) 10 kA, (230 V AC) 20 kA, (400 V AC) 10 kA, (440 V AC) 10 kA, (48 V DC) 20 kA
Rated Service Short-Circuit Breaking Capacity (Ics): (230 V AC) 15 kA, (400 V AC) 7.5 kA, (440 V AC) 7.5 kA
Rated Insulation Voltage (Ui): 440 V
Rated Impulse Withstand Voltage (Uimp): 4 kV, at 2000 m 5 kV, at Sea Level 6.2 kV
Dielectric Test Voltage: 50 / 60 Hz – 1 min 2 kV
Input Voltage Type: AC/DC
Rated Frequency (f): 50 / 60 Hz
Power Loss: 8.8 W, at Rated Operating Conditions per Pole 4.4 W
Power Supply Connection: Arbitrary
Contact Position Indication: Red ON / Green OFF
Energy Limiting Class: 3
Electrical Endurance: 10000 AC cycle
Mechanical Endurance: 20000 cycle
Terminal Type: Screw Terminals
Screw Terminal Type: Failsafe Bi-directional Cylinder-lift Terminal
Connecting Capacity: Busbar 10/10 mm², Flexible with Ferrule 0.75 … 25 mm², Flexible 0.75 … 25 mm², Rigid 0.75 … 35 mm², Stranded 0.75 … 35 mm²
Tightening Torque: 2.8 N·m
Recommended Screw Driver: Pozidriv 2
Mounting on DIN Rail: TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715, TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Mounting Position: any
Overvoltage Category: III
Pollution Degree: 3
Housing Material: Insulation Group II, RAL 7035
Actuator Material: Insulation Group II, Black, Sealable
Actuator Type: Toggle
Actuator Marking: I / O
Accessories Available: Yes
Technical UL/CSA
Maximum Operating Voltage UL/CSA: 110 V DC, 480Y / 277 V AC
Interrupting Rating acc. to UL1077: (277 V AC) 6 kA, (480Y / 277 V AC) 6 kA, (240 V) 10 kA
Connecting Capacity UL/CSA: Busbar 18-8 AWG, Conductor 18-4 AWG
Tightening Torque UL/CSA: 18 in·lb
Environmental
Ambient Air Temperature: Operation -25 … +55 °C, Storage -40 … +70 °C
Degree of Protection: IP20, Enclosure with Cover IP40
Resistance to Shock acc. to IEC 60068-2-27: 25g 2 shocks 13 ms
Resistance to Vibrations: 20 Cycles with Load 0.8 In: 5g 5 … 150 … 5 Hz
RoHS Information: Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
WEEE Category: 5. Small Equipment (No External Dimension More Than 50 cm)
Dimensions
Product Net Width: 35 mm
Product Net Height: 88 mm
Product Net Depth / Length: 69 mm
Product Net Weight: 0.24 kg
Built-In Depth (t2): 69 mm
Width in Number of Modular Spacings: 2
Ordering
Package Level 1 Units: carton 5 piece
Package Level 1 Gross Weight: 1.24 kg
E-Number (Finland): 3210908
E-Number (Norway): 1665214
E-Number (Sweden): 2100721
Classifications
Customs Tariff Code: 85362010
UNSPSC: 39121603
ETIM 9: EC000042 – Miniature circuit breaker (MCB)
ETIM 10: EC000042 – Miniature circuit breaker (MCB)
eClass: V11.0 : 27141901
IDEA Granular Category Code (IGCC): 4897 >> Miniature circuit breakers
Object Classification Code: F