Description
TeSys F contactor – 3P (3 NO) – AC-3 – <= 440 V 185 A – coil 24 V AC
SKU: LC1F185B7
Status: Discontinued
Main
Range: TeSys
Range of product: TeSys F
Product or component type: Contactor
Device short name: LC1F
Contactor application: Motor control
Resistive load
Utilisation category: AC-3
AC-4
AC-1
Poles description: 3P
[Ue] rated operational voltage: <= 460 V DC
<= 690 V AC 50/60 Hz
[Uc] control circuit voltage: 24 V AC 40…400 Hz
[Ie] rated operational current: 275 A (at <40 °C) at <= 440 V AC-1
185 A (at <55 °C) at <= 440 V AC-3
[Uimp] rated impulse withstand voltage: 8 kV
[Ith] conventional free air thermal current: 275 A (at 40 °C)
Rated breaking capacity: 1480 A conforming to IEC 60947-4-1
[Icw] rated short-time withstand current: 1500 A 40 °C – 10 s
920 A 40 °C – 30 s
740 A 40 °C – 1 min
500 A 40 °C – 3 min
400 A 40 °C – 10 min
Associated fuse rating: 200 A aM at <= 440 V
315 A gG at <= 440 V
Average impedance: 0.33 mOhm – Ith 275 A 50 Hz
[Ui] rated insulation voltage: 1000 V conforming to IEC 60947-4-1
1500 V conforming to VDE 0110 group C
Power dissipation per pole: 12 W AC-3
25 W AC-1
Overvoltage category: III
power pole contact composition: 3 NO
Motor power kW: 90 kW at 380…400 V AC 50/60 Hz (AC-3)
100 kW at 415 V AC 50/60 Hz (AC-3)
100 kW at 440 V AC 50/60 Hz (AC-3)
110 kW at 500 V AC 50/60 Hz (AC-3)
110 kW at 660…690 V AC 50/60 Hz (AC-3)
55 kW at 220…230 V AC 50/60 Hz (AC-3)
33 kW at 400 V AC 50/60 Hz (AC-4)
Control circuit voltage limits: Operational: 0.85…1.1 Uc 40…400 Hz (at 55 °C)
Drop-out: 0.35…0.55 Uc 40…400 Hz (at 55 °C)
Mechanical durability: 10 Mcycles
Inrush power in VA: 950…1180 VA, 40…400 Hz cos phi 0.9 (at 20 °C)
Hold-in power consumption in VA: 8.9…10.9 VA, 40…400 Hz cos phi 0.9 (at 20 °C)
Maximum operating rate: 2400 cyc/h 55 °C
Operating time: 35 ms closing (at Uc)
130 ms opening (at Uc)
Connections – terminals: Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end
Power circuit: bar 2 cable(s) – busbar cross section: 25 x 3 mm
Power circuit: lugs-ring terminals 1 cable(s) 150 mm²
Power circuit: connector 1 cable(s) 150 mm²
Power circuit: bolted connection
Tightening torque: Control circuit: 1.2 N.m
Power circuit: 18 N.m
Mounting support: Plate
Heat dissipation: 8…9.8 W
Standards: IEC 60947-4-1
JIS C8201-4-1
EN 60947-4-1
IEC 60947-1
EN 60947-1
Product certifications: LROS (Lloyds register of shipping)
RMRoS
UL
BV
RINA
CSA
DNV
ABS
CB
Compatibility code: LC1F
Control circuit type: AC at 40…400 Hz
Complementary
IP degree of protection: IP2X front face with shrouds conforming to IEC 60529
IP2X front face with shrouds conforming to VDE 0106
Protective treatment: TH
Ambient air temperature for operation: -5…55 °C
Ambient air temperature for storage: -60…80 °C
Permissible ambient air temperature around the device: -40…70 °C
Height: 174 mm
Width: 168.5 mm
Depth: 181 mm
Operating altitude: 3000 m without derating
Net weight: 4.65 kg
Packing Units
Unit Type of Package 1: PCE
Number of Units in Package 1: 1
Package 1 Height: 18.1 cm
Package 1 Width: 16.85 cm
Package 1 Length: 17.4 cm
Package 1 Weight: 4.67 kg