Description
General Information
Extended Product Type: MS132-12
Product ID: 1SAM350000R1012
EAN: 4013614400124
Catalog Description: MS132-12 Manual Motor Starter 8.0 … 12 A
Long Description: The MS132-12 manual motor starter (also known as motor protection circuit breaker or manual motor protector) is a compact 45 mm width device with a rated operational current of Ie = 12.0 A. This device is used to manually switch on and off motors and to protect them reliably and without the need for a fuse from short-circuits, overload and phase failures. The manual motor starter offers a rated service short-circuit breaking capacity Ics = 100 kA at 400 VAC and trip class 10. Further features are the build-in disconnect function, temperature compensation, trip-free mechanism and a rotary handle with a clear switch position indication. The manual motor starter is suitable for three- and single-phase applications. The handle is lockable to protect against unauthorized changes. Auxiliary contacts, signaling contacts, undervoltage releases, shunt trips, 3-phase bus bars, power in-feed blocks and terminal spacers are available as accessory.
Ordering
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85362010
Dimensions
Product Net Width: 45 mm
Product Net Height: 97.8 mm
Product Net Depth / Length: 86.55 mm
Product Net Weight: 0.31 kg
Technical
Rated Service Short-Circuit Breaking Capacity (Ics): (230 V AC) 100 kA
(250 V DC) 3 Poles in Series 10 kA
(400 V AC) 100 kA
(440 V AC) 30 kA
(500 V AC) 20 kA
(690 V AC) 3 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu): (230 V AC) 100 kA
(400 V AC) 100 kA
(440 V AC) 30 kA
(500 V AC) 20 kA
(690 V AC) 3 kA
Rated Instantaneous Short-Circuit Current Setting (Ii): 180 A
Setting Range: 8.0 … 12 A
Rated Operational Power AC-3 (Pe): (400 V) Three Phase 5.5 kW
Rated Operational Power AC-3e (Pe): (400 V) Three Phase 5.5 kW
Rated Operational Voltage: Main Circuit 690 V AC
Main Circuit 250 V DC
Rated Operational Current (Ie): 12 A
Rated Operational Current AC-3 (Ie): 12 A
Rated Operational Current AC-3e (Ie): 12 A
Rated Operational Current DC-5 (Ie): 12 A
Rated Frequency (f): Main Circuit 50 Hz
Main Circuit 60 Hz
Rated Impulse Withstand Voltage (Uimp): Main Circuit 6 kV
Rated Insulation Voltage (Ui): 690 V
Power Loss: at Rated Operating Conditions per Pole 1.0 … 2.3 W
Number of Poles: 3P
Conventional Free-air Thermal Current (Ith): Main Circuit 12 A
Degree of Protection: Housing IP20
Main Circuit Terminals IP10
Pollution Degree: 3
Electrical Durability: 50000 cycle
Mechanical Durability: Nr. Operations 100000 cycle
Terminal Type: Screw Terminals
Standards: IEC/EN 60947-1
IEC/EN 60947-2
IEC/EN 60947-4-1
UL 60947-1
UL 60947-4-1
IEC 60335-2-40 A2L
Container Information
Package Level 1 Units: box 1 piece
Package Level 1 Width: 92 mm
Package Level 1 Depth / Length: 102 mm
Package Level 1 Height: 50 mm
Package Level 1 Gross Weight: 0.325 kg
Package Level 1 EAN: 4013614400124
External Classifications and Standards
Object Classification Code: F
ETIM 9: EC000074 – Motor protection circuit-breaker
eClass: V11.0 : 27370401
UNSPSC: 39121521