Description
Description
TeSys F contactor, 3 poles (3NO), 185A/690V AC-3, for motor applications up to 90kW@400V. It provides a low sealed consumption 380V 40-400Hz AC coil, bolt terminals for bars or cables with lugs. For high operating rates until 2400 cycles/hour and environments until 55°C, it procures high reliability and durability. It makes installation and maintenance easy thanks to its drawer-mounted coil and a large choice of add-on blocks and accessories (to be ordered separately). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).
Specifications
Main
Range: TeSys
Range of Product: TeSys F
Product or Component Type: Contactor
Device short name: LC1F
Contactor application: Resistive load
Motor control
Utilisation category: AC-3
AC-4
AC-1
Poles description: 3P
[Ue] rated operational voltage: <= 460 V DC
<= 690 V AC 50/60 Hz
[Uc] control circuit voltage: 380 V AC 40…400 Hz
[Ie] rated operational current: 275 A (at <104 °F (40 °C)) at <= 440 V AC-1
185 A (at <131 °F (55 °C)) at <= 440 V AC-3
[Uimp] rated impulse withstand voltage: 8 kV
[Ith] conventional free air thermal current: 275 A (at 104 °F (40 °C))
Rated breaking capacity: 1480 A conforming to IEC 60947-4-1
[Icw] rated short-time withstand current: 1500 A 104 °F (40 °C) – 10 s
920 A 104 °F (40 °C) – 30 s
740 A 104 °F (40 °C) – 1 min
500 A 104 °F (40 °C) – 3 min
400 A 104 °F (40 °C) – 10 min
Associated fuse rating: 200 A aM at <= 440 V
315 A gG at <= 440 V
Average impedance: 0.33 mOhm – Ith 275 A 50 Hz
[Ui] rated insulation voltage: 1000 V IEC 60947-4-1
1500 V VDE 0110 group C
Power dissipation per pole: 12 W AC-3
25 W AC-1
Overvoltage category: III
power pole contact composition: 3 NO
Motor power kW: 90 kW at 380…400 V AC 50/60 Hz (AC-3)
100 kW at 415 V AC 50/60 Hz (AC-3)
100 kW at 440 V AC 50/60 Hz (AC-3)
110 kW at 500 V AC 50/60 Hz (AC-3)
110 kW at 660…690 V AC 50/60 Hz (AC-3)
55 kW at 220…230 V AC 50/60 Hz (AC-3)
33 kW at 400 V AC 50/60 Hz (AC-4)
Control circuit voltage limits: Operational 0.85…1.1 Uc 40…400 Hz 131 °F (55 °C))
Drop-out 0.2…0.55 Uc 40…400 Hz 131 °F (55 °C))
Mechanical durability: 10 Mcycles
Inrush power in VA: 1070 VA, 40…400 Hz 0.9 68 °F (20 °C))
Hold-in power consumption in VA: 9.9 VA, 40…400 Hz 0.9 68 °F (20 °C))
Maximum operating rate: 2400 cyc/h 131 °F (55 °C)
Operating time: 35 ms closing at Uc)
130 ms opening at Uc)
Connections – terminals: Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible without cable end
Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)flexible without cable end
Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible with cable end
Control circuit screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²)flexible with cable end
Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)solid without cable end
Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)solid without cable end
Power circuit bar 2 25 x 3 mm
Power circuit lugs-ring terminals 1 0.2 in² (150 mm²)
Power circuit connector 1 0.2 in² (150 mm²)
Power circuit bolted connection
Tightening torque: Control circuit 10.6 lbf.in (1.2 N.m)
Power circuit 159.3 lbf.in (18 N.m)
Mounting Support: Plate
Heat dissipation: 8…9.8 W
Standards: EN 60947-1
IEC 60947-1
IEC 60947-4-1
JIS C8201-4-1
EN 60947-4-1
Product Certifications: RINA
LROS (Lloyds register of shipping)
DNV
BV
ABS
CCC
RMRoS
UL
CB
UKCA
Compatibility code: LC1F
Control circuit type: AC 40…400 Hz
Complementary
IP degree of protection: IP2X front face with shrouds IEC 60529
IP2X front face with shrouds VDE 0106
Protective treatment: TH
Ambient Air Temperature for Operation: 23…131 °F (-5…55 °C)
Ambient Air Temperature for Storage: -76…176 °F (-60…80 °C)
Permissible ambient air temperature around the device: -40…158 °F (-40…70 °C)
Height: 17.4 cm
Width: 16.85 cm
Depth: 18.1 cm
Operating altitude: 9842.52 ft (3000 m) without derating
Net Weight: 4.65 kg
Environment
GTIN: 3389110351569
Country of origin: CZ
Contractual warranty
Warranty: 18 months