Description
Product Name: S204M-C40
Brand: ABB
Product ID: 2CDS274001R0404
EAN: 4016779550796
Description: Miniature Circuit Breaker – S200M – 4P – 40 A – C – (AC) 10 kA
Details: System pro M compact S200M miniature circuit breakers are current limiting. They have two different tripping mechanisms, the delayed thermal tripping mechanism for overload protection and the electromechanic tripping mechanism for short circuit protection. Available in characteristics B,C,D,K,Z; configurations 1P,1P+N,2P,3P,3P+N,4P; breaking capacities up to 10 kA at 230/400 V AC; rated currents up to 63 A. Complies with IEC/EN 60898-1 and IEC/EN 609 47-2, suitable for residential, commercial and industrial uses. Bottom-fitting auxiliary contact can be mounted on S200M to save 50% space.
Electrical Technical Data: Dielectric test voltage 2 kV at 50/60 Hz for 1 min; rated ultimate short-circuit breaking capacity 25 kA at 230 V AC, 15 kA at 400 V and 440 V AC; rated service short-circuit breaking capacity 7.5 kA at 230 V AC; power supply connection arbitrary; contact position indication red ON / green OFF; energy limiting class 3; electrical endurance 10000 AC cycles; mechanical endurance 20000 cycles; protected poles 4; number of poles 4; tightening torque 2.8 N·m; actuator toggle type with I / O marking and insulation group II, black, sealable; recommended screwdriver Pozidriv 2; accessories available; connecting capacity includes busbar 10/10 mm², flexible with ferrule 0.75 to 25 mm², rigid and stranded 0.75 to 35 mm²; installation size 1 modular spacing per DIN 43880; terminal type screw terminals.
Electrical Characteristics: Tripping characteristic C; rated operational voltage 400 V AC per IEC 60898-1 and 440 V AC per IEC 60947-2; operational voltage max 125 V DC and 440 V AC; minimum operational voltage 12 V AC/DC; rated insulation voltage 440 V; rated impulse withstand voltage 4 kV standard, 5 kV at 2000 m altitude, 6.2 kV at sea level; input voltage type AC/DC; rated current 40 A; rated short-circuit capacity 10 kA AC at 230 V; conditional short-circuit current 15 kA at 230 V and 25 kA at 400 V; frequency 50 Hz; rated frequency 50/60 Hz; power loss total 19.2 W and 4.8 W per pole; overvoltage category III; I²t characteristic typical for S200 series B-C type let-through energy.
Mechanical Design: Housing material insulation group II, RAL 7035.
UL/CSA Specifications: Max operating voltage 125 V DC, 480Y/277 V AC; interrupting rating UL1077 10 kA at 125 V DC, 6 kA at 277 V and 480Y/277 V AC; connecting capacity busbar 14-8 AWG, conductor 14-4 AWG; tightening torque 18 in·lb.
Environmental Compliance: RoHS compliant per EU Directive 2011/65/EU and amendment 2015/863; RoHS date 2024-02-28; REACH does not contain restricted substances; REACH date 2025-09-17; conflict minerals reporting template ID 9008497a-14f6-4cfd-83c5-11cf3bc660d1 Germany; WEEE category 5 small equipment under 50 cm; product intended for business to business use; ambient operating temperature -25 to +55 °C; storage temperature -40 to +70 °C; reference ambient temperature 30 °C; protection degree IP20 / IP40 with enclosure cover; pollution degree 3; environmental cycles 28 with temperatures and humidity ranges; vibration resistance 5g 5-150-5 Hz; shock resistance 25 g two shocks 13 ms.
Dimensions: Width 7 cm, height 8.8 cm, depth 6.9 cm, weight 0.48 kg; pole weight 0.125 kg; width 4 modular spacings; built-in depth 6.9 cm.
Ordering Info: Package level 1 unit carton with 1 piece, gross weight 0.5 kg; E-Numbers Norway 1665740, Sweden 2101268.
Certifications and Standards: Complies with IEC/EN 60898-1, CSA 22.2 No. 235, IEC/EN 60947-2, UL 1077; certification agencies EN and IEC; standardization bodies EN and IEC; ETIM code EC000042 miniature circuit breaker; UNSPSC code 39121603; eClass V11.0 27141901; IDEA category 4897 miniature circuit breakers; customs tariff code 39121603.
Installation: Mounting on TH35-15 or TH35-7.5 mm DIN rail per IEC 60715; mounting position any; includes instruction manuals for S200 and S300.