Description
MS116-16 Manual Motor Starter
Manufacturer: ABB
The MS116-16 manual motor starter (also known as motor protection circuit breaker or manual motor protector) is a compact 4.5 cm width device with a rated operational current of Ie = 16.0 A. It is used to manually switch on and off motors and protect them reliably without the need for a fuse from short-circuits, overload and phase failures.
Rated service short-circuit breaking capacity (Ics): 16 kA at 400 V AC
Trip class: 10A
Features include build-in disconnect function, temperature compensation, trip-free mechanism, and a rotary handle with clear switch position indication. Suitable for three- and single-phase applications.
Auxiliary contacts, signaling contacts, undervoltage releases, shunt trips, 3-phase bus bars, power in-feed blocks and locking devices for protection against unauthorized changes are available as accessories.
Dimensions (cm): Width 4.5, Height 9.0, Depth 8.56
Weight: 0.265 kg
Rated Ultimate Short-Circuit Breaking Capacity (Icu): 16 kA at 400 V AC
Rated Operational Power AC-3 (Pe): 7.5 kW at 400 V Three Phase
Rated Operational Voltage: 690 V AC Main Circuit
Number of Poles: 3P
Degree of Protection: Housing IP20, Main Circuit Terminals IP10
Pollution Degree: 3
Terminal Type: Screw Terminals
Tightening Torque: 0.8 … 1.2 N·m Main Circuit
Mounting: DIN Rail TH35-15 (3.5 x 1.5 cm) or TH35-7.5 (3.5 x 0.75 cm) acc. to IEC 60715
Standards: IEC/EN 60947-1, IEC/EN 60947-2, IEC/EN 60947-4-1, UL 60947-1, UL 60947-4-1, IEC 60335-2-40 A2L
Customs Tariff Code: 85362010