Description
TF42-0.41 Thermal Overload Relay
The TF42-0.41 thermal overload relay is an economic electromechanical protection device for the main circuit. It offers reliable and fast protection for motors in the event of overload or phase failure. The device has trip class 10. Features include temperature compensation, trip contact (NC), signal contact (NO), automatic or manual reset selectable, trip-free mechanism, STOP function, and trip indication. The overload relays are connected directly to the block contactors. Single mounting kits are available as accessory.
Setting Range: 0.31 … 0.41 A
Rated Operational Voltage: Auxiliary Circuit 600 V AC/DC; Main Circuit 690 V AC; Main Circuit 600 V DC
Rated Operational Current (Ie): 0.41 A
Rated Frequency (f): Auxiliary Circuit 50 Hz, 60 Hz, DC; Main Circuit 50 Hz, 60 Hz
Rated Impulse Withstand Voltage (Uimp): Auxiliary Circuit 6 kV; Main Circuit 6 kV
Rated Insulation Voltage (Ui): 690 V
Number of Poles: 3P
Number of Auxiliary Contacts NC/NO: 1 NC, 1 NO
Number of Protected Poles: 3
Conventional Free-air Thermal Current (Ith): Auxiliary Circuit NC 6 A, NO 4 A
Rated Operational Current AC-15 (Ie): (120 V) NC 3 A, NO 0.5 A; (240 V) NC 3 A, NO 0.5 A; (400 V) NC 0.75 A, NO 0.5 A; (500 V) NC 0.75 A, NO 0.5 A
Rated Operational Current DC-13 (Ie): (125 V) NC 0.55 A, NO 0.55 A; (24 V) NC 1.25 A, NO 1.25 A; (250 V) NC 0.27 A, NO 0.27 A; (500 V) NC 0.15 A, NO 0.15 A; (60 V) NC 0.55 A, NO 0.55 A
Degree of Protection: IP20
Pollution Degree: 3
Connecting Capacity Auxiliary Circuit: Flexible with Ferrule 1/2x 0.75 … 2.5 mm²; Flexible with Insulated Ferrule 1x 0.75 … 2.5 mm²; and others
Connecting Capacity Main Circuit: Flexible with Ferrule 1/2x 0.75 … 4 mm²; Flexible with Insulated Ferrule 1/2x 0.75 … 4 mm²; and others
Tightening Torque: Auxiliary Circuit 1 … 1.2 N·m; Main Circuit 1.5 … 2.5 N·m
Wire Stripping Length: Auxiliary Circuit 0.9 cm; Main Circuit 1.2 cm
Recommended Screw Driver: Main Circuit Pozidriv 2
Power Loss (per pole at rated conditions): 1.1 … 2.0 W
Suitable For: AF09, AF12, AF16, AF26, AF30, AF38
Standards: IEC/EN 60947-1, IEC/EN 60947-4-1, IEC/EN 60947-5-1, UL 60947-1, UL 60947-4-1, IEC 60335-2-40 A2L
Operating Temperature Range: -25 … +60 °C (operation and compensated), Storage: -50 … +80 °C
Maximum Operating Altitude: 2000 m
Resistance to Shock: 11 ms Pulse 25g; Resistance to Vibrations: 5g 3 … 150 Hz
RoHS Compliance: Following EU Directive 2011/65/EU and Amendment 2015/863
WEEE Category: 5. Small Equipment (No External Dimension More Than 50 cm)
Package Level 1 Dimensions (WxHxD): 4.8 cm x 9.2 cm x 7.8 cm
Package Level 1 Gross Weight: 0.145 kg
Package Level 2 Units: carton 40 piece; Dimensions (WxHxD): 28 cm x 21 cm x 39.5 cm; Gross Weight: 7.346 kg