Description
TF42-35 Thermal Overload Relay
The TF42-35 thermal overload relay is an economic electromechanical protection device for the main circuit. It offers reliable and fast protection for motors in the event of overload or phase failure. The device has trip class 10.
Key features include: temperature compensation, trip contact (NC), signal contact (NO), automatic or manual reset selectable, trip-free mechanism, STOP function, and trip indication.
The overload relays are connected directly to the block contactors. Single mounting kits are available as accessory.
Technical specifications:
- Setting Range: 29 … 35 A
- Rated Operational Voltage: Auxiliary Circuit 600 V AC/DC, Main Circuit 690 V AC, 600 V DC
- Rated Operational Current: 35 A
- Rated Frequency: Auxiliary Circuit 50 Hz, 60 Hz, DC; Main Circuit 50 Hz, 60 Hz
- Rated Impulse Withstand Voltage: 6 kV
- Rated Insulation Voltage: 690 V
- Number of Poles: 3
- Auxiliary Contacts: 1 NC and 1 NO
- Degree of Protection: IP20
- Pollution Degree: 3
- Tightening Torque: Auxiliary Circuit 1 … 1.2 N·m, Main Circuit 2.5 … 2.7 N·m
- Wire Stripping Length: Auxiliary Circuit 9 mm, Main Circuit 12 mm
- Recommended Screw Driver: Main Circuit Pozidriv 2
- Power Loss per Pole: 2.1 … 2.8 W
- Suitable For: AF09, AF12, AF16, AF26, AF30, AF38
- Standards: IEC/EN 60947-1, IEC/EN 60947-4-1, IEC/EN 60947-5-1, UL 60947-1, UL 60947-4-1, IEC 60335-2-40 A2L
- Environmental Conditions: Operation -25 … +60 °C, Storage -50 … +80 °C, Max Operating Altitude 2000 m
Dimensions: Width 4.5 cm, Height 8.83 cm, Depth 7.05 cm
Weight: 0.145 kg
Customs Tariff Code: 85364900