Description
Block Contactor AF40-30-11-13
The AF40-30-11-13 is a 3-pole contactor suitable for 690 V IEC or 600 V UL applications with pre-mounted auxiliary contacts and screw terminals. It controls motors up to 18.5 kW at 400 V AC (AC-3) or 30 hp at 480 V UL. The device can switch power circuits up to 70 A (AC-1) or 60 A UL general use.
Key Features: Wide control voltage range from 100 to 250 V (50/60 Hz and DC) which manages large control voltage variations, reducing panel energy consumption and ensuring reliable operation in unstable networks. Built-in surge protection offers a compact and efficient solution. The device has a block type design allowing easy extension with add-on auxiliary contact blocks and a wide range of accessories.
Dimensions: Width 6.7 cm, Depth 11.1 cm, Height 12.55 cm.
Weight: 0.99 kg.
Electrical Ratings: Rated operational voltage main circuit and auxiliary circuit 690 V. Rated frequency 50/60 Hz. Conventional free-air thermal current 105 A. Rated operational current AC-1 up to 70 A at 690 V and 40 °C. Rated operational current AC-3 up to 40 A at 415/440 V and 60 °C. Rated operational power AC-3 up to 18.5 kW at 400 V and up to 22 kW at 415 to 690 V.
Control circuit voltage: 100 to 250 V at 50/60 Hz and DC. Coil consumption average holding value 4 V·A at 50/60 Hz, 2 W DC.
Mechanical and Electrical Switching Frequency: Max electrical switching frequency of 600 cycles/hour AC-1, 1200 AC-15 and AC-3, 900 DC-13 cycles/hour. Max mechanical switching frequency 3600 cycles/hour.
Mounting: TH35-15 and TH35-7.5 mm DIN rails acc. to IEC 60715 or by screws (2x M4 or M6).
Connection Capacity: Main circuit 4 to 35 mm² flexible with ferrule or 6 to 35 mm² rigid stranded; Auxiliary circuit 0.75 to 2.5 mm² flexible and rigid; Control circuit 0.75 to 2.5 mm² flexible and rigid. Wire stripping lengths: Auxiliary and control circuits 10 mm, main circuit 16 mm.
Degree of Protection: Auxiliary and coil terminals IP20, main terminals IP10 according to IEC 60529.
Environmental: Operating ambient temperature -40 to 70 °C, storage -60 to 80 °C. Climatic withstand category B according to IEC 60947-1 Annex Q. Maximum altitude 3000 m without derating. Pollution degree 3.
Standards and Certifications: IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60335-2-40 LZGH2 A2L, UL 60947-1 and 4-1, CSA C22.2 standards, plus multiple international certificates including CCC, CB, UL, DNV, and others.
Customs Tariff Code: 85364900.