Description
Product: A1B 125 TMF 40-400 3p F F
Extended Product Type: A1B 125 TMF 40-400 3p F F
Catalog Description: A1B 125 TMF 40-400 3p F F
Long Description: C.BREAKER FORMULA A1B 125 FIXED THREE-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMF R 40-400 A
Product Main Type: SACE FORMULA
Product Type: Automatic Circuit Breaker
Product Name: Moulded Case Circuit Breaker
Order Code US and Canada: AAB040TW
Minimum Order Quantity: 1 piece
Customs Tariff Code: 85362090
Dimensions (W x H x D): 7.62 cm x 13.0 cm x 6.0 cm
Weight: 0.776 kg
Package Level 1 Units: 1 piece
Package Level 1 Dimensions (W x H x D): 13.65 cm x 12.4 cm x 11.05 cm
Package Level 1 Gross Weight: 0.8 kg
Electrical Durability: 1500 cycle
Mechanical Durability: 8500 cycle
Number of Poles: 3P
Opening Time: CB with SOR 15 ms, CB with UVR 15 ms
Power Loss: 4.5 W at Rated Operating Conditions per Pole
Rated Current (In): 40 A Main Circuit
Rated Impulse Withstand Voltage (Uimp): 6 kV
Rated Insulation Voltage (Ui): 690 V
Rated Operational Voltage: 550 V AC, 250 V DC
Rated Service Short-Circuit Breaking Capacity (Ics): (240 V AC) 12.5 kA, (380 V AC) 9 kA, (415 V AC) 5 kA, (440 V AC) 5 kA, (480 V AC) 5 kA, (500 V AC) 2.5 kA, (250 V DC) 2 Poles in Series 2.5 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu): (240 V AC) 25 kA, (380 V AC) 18 kA, (415 V AC) 18 kA, (440 V AC) 15 kA, (480 V AC) 10 kA, (500 V AC) 5 kA, (250 V DC) 5 kA
Rated Uninterrupted Current (Iu): 125 A
Release: TMF
Release Type: TM
Short-Circuit Performance Level: B
Standards: IEC
Sub-type: A1
Terminal Connection Type: Front