Description
A1B 125 TMF 32-400 3p F F
Main Type: SACE FORMULA
Product Type: Automatic Circuit Breaker
Version: F
Extended Product Type: A1B 125 TMF 32-400 3p F F
EAN: 8015644029982
Description: C.BREAKER FORMULA A1B 125 FIXED THREE-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMF R 32-400 A
Order Code US and Canada: AAB032TW
Minimum Order Quantity: 1 piece
Customs Tariff Code: 85362090
Dimensions (Net): Width 7.62 cm, Height 13 cm, Depth/Length 6 cm
Weight (Net): 0.786 kg
Package Level 1: Units 1 piece, Width 13.65 cm, Height 12.4 cm, Depth/Length 11.05 cm, Gross Weight 0.8 kg
Number of Poles: 3
Durability: Electrical 1500 cycles, Mechanical 8500 cycles
Opening Time: CB with SOR 15 ms, CB with UVR 15 ms
Power Loss at Rated Operating Conditions per Pole: 4 W
Rated Current (In) Main Circuit: 32 A
Rated Impulse Withstand Voltage (Uimp): 6 kV
Rated Insulation Voltage (Ui): 690 V
Rated Operational Voltage: 550 V AC, 250 V DC
Rated Service Short-Circuit Breaking Capacity (Ics): 12.5 kA at 240 V AC, 9 kA at 380 V AC, 5 kA at 415 V AC, 5 kA at 440 V AC, 5 kA at 480 V AC, 2.5 kA at 500 V AC, 2.5 kA at 250 V DC (2 Poles in Series)
Rated Ultimate Short-Circuit Breaking Capacity (Icu): 25 kA at 240 V AC, 18 kA at 380 V AC, 18 kA at 415 V AC, 15 kA at 440 V AC, 10 kA at 480 V AC, 5 kA at 500 V AC, 5 kA at 250 V DC
Rated Uninterrupted Current (Iu): 125 A
Release: TMF
Release Type: TM
Short-Circuit Performance Level: B
Standards: IEC
Sub-type: A1
Terminal Connection Type: Front
Documentation: Data Sheet Document Code 1SDC210032D0204, Declaration of Conformity CE EC Declaration of Conformity Formula DSA A1, Wiring Diagram FORMULA A1-A2, Installation Instructions Formula A1/III-IV
Classifications: ETIM 9 and 10 EC000228 – Power circuit-breaker for trafo/generator/installation protection, Object Classification Code Q, WEEE Category 5 Small Equipment (No External Dimension More Than 50 cm), eClass V11.1 : 27370409