Description
Product Name: E4.2N 3200 Ekip Dip LI 4p F HR
Manufacturer: ABB
Product ID: 1SDA071771R1
EAN: 8015644756215
Description: C.BREAKER SACE EMAX2 E4.2N 3200 fixed four-pole with terminals rear horizontal and solid-state release in AC EKIP/DIP-LI R 3200 fitted with: 4 auxiliary contact and circuit breaker in position open-closed.
Extended Product Type: E4.2N 3200 Ekip Dip LI 4p F HR
Product Type: Air Circuit Breaker, Version F
Main Type: SACE Emax 2
Rated Current (In): 3200 A
Rated Operational Voltage: 690 V AC
Rated Insulation Voltage (Ui): AC 1000 V
Rated Impulse Withstand Voltage (Uimp): 12 kV (according to IEC 60947-2)
Number of Poles: 4
Power Loss: 425 W
Rated Ultimate Short-Circuit Breaking Capacity (Icu): 66 kA at 400-690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics): 66 kA (100% of Icu)
Rated Short-time Withstand Current Low Voltage (Icw): 66 kA for 1 s, 50 kA for 3 s
Rated Uninterrupted Current (Iu): 3200 A
Connecting Capacity: 3000 mm²
Terminal Connection Type: Rear flat horizontal, Bolt type
Tightening Torque: 70 N·m
Release Type: Ekip Dip LI (EL)
Electrical Durability: Ue ≤ 440 V 7000 cycles; Ue 500-690 V 7000 cycles; 20 cycles per hour
Mechanical Durability: 20000 cycles; 60 cycles per hour
Neutral Pole Current: 100%
Suitable for IT Networks: Yes, 690 V
Dimensions (W x H x D): 51.0 cm x 37.1 cm x 27.0 cm
Weight: 70 kg
Package Dimensions (W x H x D): 51.5 cm x 61.0 cm x 78.5 cm
Package Weight: 77 kg
Order Code US and Canada: ZCNVENBA000A000000XX
Minimum Order Quantity: 1 piece
Customs Tariff Code: 85362090
Environmental and Compliance: ABB EcoSolutions certified; UL 2799 Zero Waste To Landfill Validation available; Recyclability Rate according to EN45555: 79.3%; Complies with REACH, RoHS Directive 2011/65/EU and Amendment 2015/863; Conflict Minerals Reporting Template (CMRT); TSCA declaration; SCIP Italy registry.
Standards: IEC
Certifications: No certification needed for ATEX, CSA, UL, VDE