Description
AF190-30-00-13 Contactor by ABB
The AF190-30-00-13 is a 3 pole contactor designed for 1000 V IEC or 600 V UL applications with Main Circuit Bars. It controls motors up to 90 kW at 400 V AC (AC-3) or 125 hp at 480 V UL. It switches power circuits up to 275 A (AC-1) or 250 A UL general use. Thanks to AF technology, it features a wide control voltage range of 100-250 V (50/60 Hz and DC), effectively managing large control voltage variations and reducing panel energy consumption, ensuring distinct operations in unstable networks. The contactor includes built-in surge protection and offers a compact block type design that can be extended with add-on auxiliary contact blocks and a wide range of accessories. It comes with a Mounting kit containing necessary screws, washers, sockets for terminal connection, and mounting screws.
Dimensions (cm): Width: 10.5, Depth/Length: 15.2, Height: 19.6
Weight (kg): 2.4
Electrical Characteristics:
Number of Poles: 3P
Rated Operational Voltage: Main Circuit 1000 V
Rated Frequency: Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith): 275 A (IEC 60947-4-1, Open Contactors at 40 °C)
Rated Operational Currents AC-1 and AC-3 vary by voltage and temperature, for example, AC-1 up to 275 A at 690 V and 40 °C, AC-3 up to 190 A at 415 V and 55 °C.
Rated Operational Power AC-3 up to 132 kW (690 V), AC-3e same values.
Short-Circuit Protective Devices: gG Type Fuses 355 A
Rated Short-time Withstand Current (Icw) ranges from 275 A for 10s to 1900 A for 1 min at 40 °C in free air.
Maximum Breaking Capacity: 3300 A at 440 V, 2200 A at 690 V.
Rated Insulation Voltage: 1000 V IEC, 600 V UL/CSA.
Degree of Protection: Auxiliary Terminals IP40, Coil Terminals IP20, Main Terminals IP00 as per IEC 60529.
Mechanical Durability: 5 million operations
Rated Control Circuit Voltage: 100 … 250 V (50 Hz, 60 Hz and DC)
Coil Consumption varies with control voltage and frequency, for example holding coil at max rated voltage approx 7 V·A for AC and 2.5 V·A for DC.
Operating Limits: 0.85 x Uc Min. to 1.1 x Uc Max. at temperature ≤ 70 °C
Connecting Capacity Main Circuit: Flexible cable 2 x 50 – 95 mm², Rigid Al cable 1 x 95 – 185 mm², Rigid Cu cable 2 x 50 – 120 mm².
Tightening Torque: Cable Lug 9 N·m, Main Circuit 14 – 31 N·m.
Terminal Type: Main Circuit Bars
Customs Tariff Code: 85364900