Description
AF205-30-11-13 Contactor by ABB
The AF205-30-11-13 is a 3 pole – 1000 V IEC or 600 V UL contactor with pre-mounted auxiliary contacts and Main Circuit Bars. It controls motors up to 110 kW / 400 V AC (AC-3) or 150 hp / 480 V UL and switches power circuits up to 350 A (AC-1) or 300 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (100-250 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Surge protection is built-in, offering a compact solution. AF contactors have a block type design and can be easily extended with add-on auxiliary contact blocks and a wide range of accessories. The product includes a mounting kit containing all necessary screws, washers, sockets for connecting the terminals, and screws for mounting the device.
Dimensions: Width: 10.5 cm; Depth/Length: 15.2 cm; Height: 19.6 cm; Weight: 2.4 kg.
Electrical Characteristics: 3 NO main contacts, 0 NC main contacts; 1 NO, 1 NC auxiliary contacts; 3 poles; Rated operational main circuit voltage: 1000 V; Rated frequency: 50 / 60 Hz; Conventional free-air thermal current (Ith) acc. to IEC 60947-4-1 at 40 °C: 350 A.
Rated operational current AC-1 (Ie) varies with temperature and voltage; examples include 275 A at 1000 V 40 °C, 350 A at 690 V 40 °C, etc. Rated operational current AC-3 (Ie) examples: 205 A at 415 V 55 °C, 165 A at 690 V 55 °C, 100 A at 1000 V 55 °C. Rated operational current DC-1, DC-3, DC-5 at 110 V and 220 V with 2 or 3 poles in series, all at 275 A.
Rated operational power AC-3 ranges from 55 kW at 220/230/240 V to 160 kW at 690 V. Rated breaking capacity AC-3 is 8 x Ie AC-3; making capacity is 10 x Ie AC-3, protected by gG type fuses of 400 A.
Rated short-time withstand current low voltage (Icw) at 40 °C ambient, free air from cold state ranges from 350 A for 15 min to 2050 A for 1 s.
Maximum breaking capacities: 3500 A at 440 V and 2500 A at 690 V with cos phi=0.45 (0.35 for Ie>100 A). Rated insulation voltage is 1000 V IEC and UL/CSA standards; impulse withstand voltage 8 kV.
Max electrical switching frequency is 300 cycles/hour for AC-1 and AC-3, and 150 cycles/hour for AC-2/AC-4. Mechanical durability is 5 million cycles; max mechanical switching frequency is 300 cycles/hour.
Rated control circuit voltage: 100 to 250 V at 50 Hz, 60 Hz and DC. Coil consumption: holding 7 V·A at AC, 2.5 W at DC; pull-in 220 V·A AC, 190 W DC. Power loss at rated conditions per pole: 8 W.
Operate time: 25 to 55 ms coil energization to NO contact closing; 37 to 47 ms coil de-energization to NO contact opening.
Connecting capacity main circuit: flexible 2 x 50 to 95 mm², rigid Al-cable 1 x 95 to 185 mm², rigid Cu-cable 1 x 6 to 150 mm². Auxiliary circuit connecting capacity includes flexible and solid wires ranging 0.75 to 4 mm². Degree of protection: IP20 for coil terminals and IP00 for main terminals acc. IEC and EN standards.
Tightening torque: cable lug 18 N·m; main circuit 14 to 31 N·m. Terminal type: main circuit bars.
UL/CSA Ratings: Max operating voltage 1000 V; general use rating 275 A at 1000 V AC; horsepower rating up to 200 hp depending on voltage levels; full load amps motor use up to 192 A.
Environmental: Ambient air temperature -25 to 50 °C fitted with thermal overload relay; -40 to 70 °C without relay and for storage; Max operating altitude permissible 3000 m without derating.
Compliance and Certifications: Customs Tariff Number 85364900; Conflict Minerals, REACH, RoHS, TSCA declarations available; WEEE category 5; ABB EcoSolutions certified; recyclability rate 79.2% according to EN45555; 35% recycled metal content.