Description
DSE201 C40 A30 – N Black
Manufacturer: ABB
Product ID: 2CSR255153R1404
EAN: 8012542587729
Description: Residual Current Circuit Breaker with Overcurrent Protection DSE201 – 1P – 30 mA – 40 A – C – Type A
Details: 1P+N electronic RCBO in one-module width for the protection of end user single-phase circuits against overload and short-circuit currents; protection against the effects of sinusoidal alternating earth fault currents; protection against indirect contacts and additional protection against direct contacts (with sensitivity = 30 mA). Presence of neutral (blue or black) and functional earth (white) flying leads. The neutral is unswitched.
Customs Tariff Code: 85361010
Technical Specifications:
Type of Residual Current: Type A
Maximum Operating Voltage: 264 V
Test Voltage: 19.5 – 26.4 V
Dielectric Test Voltage: 2 kV
Rated Residual Breaking Capacity: 6 kA
Rated Service Short-Circuit Breaking Capacity (Ics): 6 kA
Maximum Surge Current: 0.25 kA
Power Supply Connection: Bottom
Contact Position Indication: Red ON / Green OFF
Energy Limiting Class: 3
Electrical Endurance: 10000 cycles
Mechanical Endurance: 20000 cycles
Number of Protected Poles: 1
Number of Poles: 1P
Number of Modular Spacings per DIN Rail: 1
Operating Characteristic: Instantaneous
Position of Neutral Terminals: Right
Tightening Torque: Top 1.2 N·m, Bottom 2.8 N·m
Actuator Type: Toggle – Insulation group IIIA, black, sealable in ON-OFF positions
Earthing Switch Type: Undelayed
Housing Type: Insulation group II, RAL 7035
Screw Terminal Type: Failsafe Bi-directional Cylinder-lift Terminal
Connecting Capacity: Busbar 10 mm², Rigid 1 to 25 mm², Flexible 1 to 16 mm²
Rated Cross-Section: Multi-Wired 1 to 25 mm², Solid-Core 25 mm²
Wire Stripping Length: Top 11 mm, Bottom 12.5 mm
Terminal Type: Screw Terminals
Short-Circuit Current Rating (SCCR): 0.03 A
Tripping Characteristic: C
Rated Operational Voltage: 230 / 240 V AC
Rated Insulation Voltage (Ui): 500 V
Rated Impulse Withstand Voltage (Uimp): 4 kV
Input Voltage Type: AC
Rated Current (In): 40 A
Rated Residual Current: 30 mA
Rated Short-Circuit Capacity: 6 kA
Rated Conditional Short-Circuit Current (Inc): 6 kA
Rated Frequency: 50 to 60 Hz
Power Loss: Total 5.5 W
Overvoltage Category: III
Dimensions:
Width: 1.8 cm
Height: 10 cm
Depth: 6.9 cm
Built-In Depth (t2): 6.89 cm
Weight: 0.18 kg
Environmental and Compliance:
Ambient Air Temperature: Operation -25 to 55 °C, Storage -40 to 70 °C
Reference Ambient Air Temperature: 30 °C
Degree of Protection: Terminals IP20, Housing IP40
Pollution Degree: 2
Environmental Conditions: 28 cycles with 55 °C / 90-96 % and 25 °C / 95-100 % humidity
Resistance to Vibrations: 20 Cycles with Load 0.8 In: 5g or 0.35mm 5 to 150 Hz
Resistance to Shock acc. to IEC 60068-2-27: 30g / 2 shocks / 13 ms
RoHS Declaration: Following EU Directive 2011/65/EU
REACH Information: Contains substances > 0.1 mass percentage
Package Information: box 1 piece, Gross Weight 0.22 kg
Mounting: DIN-Rail, Mounting Position: Any
Standards: IEC 61009-1, IEC 61009-2-2, AS/NZS 61009.1