Description
PSTX142-600-70 Softstarter
The softstarter PSTX142-600-70 has a rated maximum operational current of 142 A with an operating voltage span from 208…600 V AC. The rated control voltage range is between 100…250 V AC at 50/60 Hz. PSTX features a three-phase control soft start and stop through a voltage or a torque ramp. It has built-in bypass for easy installation and energy saving. A RUN, TOR and Event signal is available from relay outputs in NO (normally open state). The PSTX includes functions such as current limit, kickstart, analog output, EOL, motor heating, and pump cleaning. It also features jog, braking, stand-still brake, diagnostics, sequence start, and emergency/fire pump mode as standard.
To interact with PSTX, it has a detachable full graphic display with IP66 and 4x outdoor rating. Communication can occur via hardwire inputs Start/Stop/Reset of fault and three programmable digital inputs. A popular option is the built-in Fieldbus communication Modbus RTU including optional ANYBUS modules with major protocols such as Profinet, Profibus, Modbus TCP, Ethernet IP and others. Another way to communicate is by using an external adaptor and a Fieldbus plug.
PSTX is a complete alternative for any motor starting application. It is suitable for medium to large-sized three-phase motors with nominal currents from 30…1250 A inline connection or 52…2160 A inside delta connection. Typical applications include pumps, fans, compressors, and conveyors.
Product dimensions: Width 19.9 cm, Height 37.7 cm, Depth 28.3 cm. Weight 7 kg.
Rated operational power (In-Line connection): 37 kW at 230 V, 75 kW at 400 V, 90 kW at 500 V.
Rated operational power (Inside delta connection): 75 kW at 230 V, 132 kW at 400 V, 160 kW at 500 V. Rated operational current inside delta is 245 A.
Overload Protection: Built-in electronic overload protection with integrated electronic overload time-to-cool.
Starting capacity at maximum rated current (Ie): 4 times Ie for 10 seconds.
Ramp time: 1 to 120 seconds. Initial voltage during start adjustable from 10% to 99%, step down voltage special ramp from 100% to 10%. Current limit function adjustable from 1.5 to 7.5 times Ie.
Includes signal relays for run, bypass, fault and overload. Analog outputs: 0–10 V, 0–20 mA, 4–20 mA. LED signal indications: Ready to start/standby (green), running (green), protection (yellow), fault (red).
Communications supported: Modbus-RTU, Modbus-TCP, Ethernet-IP, EtherCAT, DeviceNet, CANopen, Profibus, Profinet, BACnet-IP, BACnet-MSTP.
Degree of protection: According to IEC 60529, IEC 60947-1, EN 60529; main terminals IP00.
Terminal type: Main circuit bars; hole diameter for main circuit connections 8.5 mm; control and supply circuits support rigid 1 x 2.5 mm² connections. Tightening torque for main circuit is 14 N·m.
Protection functions: Bypass open protection, current imbalance, current underload, dual overload, earth/ground fault protection, electronic overload, extension IO failure, fieldbus failure, HMI failure, locked rotor, max number of starts/hour, over voltage, phase reversal, power factor underload, PT-100 and PTC connections, too long current limit, too long start time, under voltage, user defined, voltage imbalance.
Warnings: Current imbalance, current underload, electronic overload time-to-trip, EOL, faulty fan, locked rotor, motor runtime limit, over voltage, phase loss (standby), power factor underload, short circuit (limp mode), total harmonic distortion voltage, thyristor overload (SCR), under voltage, voltage imbalance.
Horsepower rating UL/CSA: 40 Hp (200-208 V AC), 50 Hp (220-240 V AC), 100 Hp (440-480 V AC), 125 Hp (550-600 V AC).
Maximum operating voltage UL/CSA: Main circuit 600 V.
Environmental temperatures: Operation -25 to +60 °C, Storage -40 to +70 °C.
Customs Tariff Code: 85371091.