| Weight | 3.9 kg |
|---|
| Dimensions | 23.8 × 16.6 × 18 cm |
|---|
| Product ID | 1SFL527102R1311 |
|---|
| Catalog Description | AF205-40-11-13 Contactor |
|---|
| Customs Tariff Number | 85364900 |
|---|
| Number of Main Contacts NO | 4 |
|---|
| Number of Main Contacts NC | 0 |
|---|
| Number of Auxiliary Contacts NO | 1 |
|---|
| Number of Auxiliary Contacts NC | 1 |
|---|
| Number of Poles | 4P |
|---|
| Rated Operational Voltage | Main Circuit 1000 V |
|---|
| Rated Frequency | Main Circuit 50 / 60 Hz |
|---|
| Conventional Free air Thermal Current Ith | 350 |
|---|
| Rated Operational Current AC 1 Ie | {
"1000_V_40_C": 275,
"1000_V_60_C": 250,
"1000_V_70_C": 200,
"690_V_40_C": 350,
"690_V_60_C": 300,
"690_V_70_C": 240
} |
|---|
| Rated Operational Current AC 3 Ie | {
"415_V_55_C": 205,
"440_V_55_C": 205,
"380_400_V_55_C": 205,
"220_230_240_V_55_C": 205
} |
|---|
| Rated Operational Power AC 3 Pe | {
"415_V": 110,
"440_V": 132,
"380_400_V": 110,
"220_230_240_V": 55
} |
|---|
| Rated Breaking Capacity AC 3 | 8 x Ie AC-3 |
|---|
| Rated Breaking Capacity AC 3e | 8.5 x Ie AC-3e |
|---|
| Rated Making Capacity AC 3 | 10 x Ie AC-3 |
|---|
| Rated Making Capacity AC 3e | 12 x Ie AC-3e |
|---|
| Short-Circuit Protective Devices | gG Type Fuses 400 A |
|---|
| Rated Short-time Withstand Current Low Voltage Icw | {
"10_s": 350,
"15_min": 947,
"1_min": 2050,
"1_s": 1640,
"30_s": 670
} |
|---|
| Maximum Breaking Capacity | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 3500 A |
|---|
| Rated Insulation Voltage Ui | acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V, acc. to UL/CSA 600 V |
|---|
| Rated Impulse Withstand Voltage Uimp | Main Circuit 8 kV |
|---|
| Maximum Electrical Switching Frequency | {
"AC-1": "300 cycles per hour",
"AC-3": "300 cycles per hour"
} |
|---|
| Mechanical Durability | 5000000 |
|---|
| Maximum Mechanical Switching Frequency | 300 cycles per hour |
|---|
| Coil Operating Limits | (acc. to IEC 60947-4-1) 0.85 x Uc Min. … 1.1 x Uc Max. (at θ ≤ 70 °C) |
|---|
| Rated Control Circuit Voltage Uc | 50 Hz 100 … 250 V, 60 Hz 100 … 250 V, DC Operation 100 … 250 V |
|---|
| Coil Consumption | {
"Holding_at_Max_Rated_Control_Circuit_Voltage_50_Hz": "7 V·A",
"Holding_at_Max_Rated_Control_Circuit_Voltage_60_Hz": "7 V·A",
"Holding_at_Max_Rated_Control_Circuit_Voltage_DC": "2.5 W",
"Pull-in_at_Max_Rated_Control_Circuit_Voltage_50_Hz": "220 V·A",
"Pull-in_at_Max_Rated_Control_Circuit_Voltage_60_Hz": "220 V·A",
"Pull-in_at_Max_Rated_Control_Circuit_Voltage_DC": "190 W"
} |
|---|
| Power Loss | at Rated Operating Conditions per Pole 25 W |
|---|
| Operate Time | {
"Between_Coil_De-energization_and_NO_Contact_Opening": "45 … 80 ms",
"Between_Coil_Energization_and_NO_Contact_Closing": "25 … 60 ms"
} |
|---|
| Connecting Capacity Main Circuit | {
"Flexible": "2 x 50 … 95 mm²",
"Rigid_Al-Cable": "1 x 95 … 185 mm²",
"Rigid_Cu-Cable_1": "1 x 6 … 150 mm²",
"Rigid_Cu-Cable_2": "2 x 50 … 120 mm²"
} |
|---|
| Connecting Capacity Auxiliary Circuit | {
"Flexible_with_Ferrule": "2x 0.75 … 2.5 mm²",
"Flexible_with_Insulated_Ferrule": "2x 0.75 … 2.5 mm²",
"Flexible": "2×0.75 … 2.5 mm²",
"Solid": "2 x 1 … 4 mm²",
"Stranded": "2 x 1 …. 4 mm²"
} |
|---|
| Degree of Protection | {
"Auxiliary_Terminals": "IP40",
"Coil_Terminals": "IP20",
"Main_Terminals": "IP00"
} |
|---|
| Tightening Torque | {
"Cable_Lug": "9 N·m",
"Main_Circuit": "14 … 31 N·m"
} |
|---|
| Terminal Type | Main Circuit: Bars |
|---|
| Product Main Type | Block Contactor |
|---|
| Maximum Operating Voltage UL CSA | Main Circuit 600 V |
|---|
| General Use Rating UL CSA | (1000 V AC) 275 A |
|---|
| Horsepower Rating UL CSA | {
"200_208_V_AC_Three_Phase": "30 Hp",
"200_V_AC_Three_Phase": "60 hp",
"208_V_AC_Three_Phase": "60 hp",
"220_240_V_AC_Three_Phase": "30 Hp",
"220_240_V_AC_Three_Phase_75_hp": "75 hp",
"440_480_V_AC_Three_Phase": "75 Hp",
"440_480_V_AC_Three_Phase_150_hp": "150 hp",
"550_600_V_AC_Three_Phase": "100 Hp",
"550_600_V_AC_Three_Phase_200_hp": "200 hp"
} |
|---|
| Ambient Air Temperature | {
"With_Thermal_O_L_Relay": "-25 … 50 °C",
"Without_Thermal_O_L_Relay": "-40 … 70 °C",
"For_Storage": "-40 … 70 °C"
} |
|---|
| Maximum Operating Altitude Permissible | 3000 |
|---|
| Conflict Minerals Reporting Template | Available |
|---|
| REACH Declaration | Available |
|---|
| RoHS Declaration | Available |
|---|
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
|---|
| Toxic Substances Control Act TSCA | Available |
|---|
| WEEE B2C B2B | Business To Business |
|---|
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
|---|
| ABB EcoSolutions | Yes |
|---|
| ABB Site Meeting Group Waste To Landfill Target | Non-hazardous waste is sent to a landfill, where there is no alternative option available within 100km of a facility |
|---|
| End Of Life Disassembling Instructions | Available |
|---|
| Environmental Product Declaration EPD | Available |
|---|
| Improved Energy Efficiency for Customers | Product requires less energy to operate compared to similar product on market or older products from the same line |
|---|
| Recyclability Rate of the Product acc EN45555 | 79.2 % |
|---|
| Sustainable Material Content in Product wt | {
"Recycled_Metal": "35 %"
} |
|---|
| Certificates and Declarations | {
"ABS_Certificate": "Available",
"BV_Certificate": "Available",
"CB_Certificate": "Available",
"CQC_Certificate": "Available",
"Declaration_of_Conformity_CCC": "Available",
"Declaration_of_Conformity_CE": "Available",
"Declaration_of_Conformity_UKCA": "Available",
"EAC_Certificate": "Available",
"LR_Certificate": "Available",
"PRS_Certificate": "Available",
"RINA_Certificate": "Available",
"RMRS_Certificate": "Available",
"UL_Certificate": "Available"
} |
|---|
| Package Level 1 Units | box 1 piece |
|---|
| Package Level 1 Width | 16.6 |
|---|
| Package Level 1 Depth Length | 23.8 |
|---|
| Package Level 1 Height | 18 |
|---|
| Package Level 1 Gross Weight | 3.9 |
|---|
| Package Level 1 EAN | 7320500503706 |
|---|
| Object Classification Code | Q |
|---|
| ETIM 7 | EC000066 – Power contactor, AC switching |
|---|
| ETIM 8 | EC000066 – Power contactor, AC switching |
|---|
| ETIM 9 | EC000066 – Power contactor, AC switching |
|---|
| eClass | V11.0 : 27371003 |
|---|
| UNSPSC | 39121529 |
|---|
| IDEA Granular Category Code IGCC | 4758 >> Iec Contactors |
|---|
| E Number Finland | 3707214 |
|---|
| E Number Norway | 4117785 |
|---|
| E Number Sweden | 3210335 |
|---|