| Weight |
3.9 kg |
| Dimensions |
23.8 × 16.6 × 18 cm |
| Product ID |
1SFL527102R1311
|
| Catalog Description |
AF205-40-11-13 Contactor
|
| Customs Tariff Number |
85364900
|
| Number of Main Contacts NO |
4
|
| Number of Main Contacts NC |
0
|
| Number of Auxiliary Contacts NO |
1
|
| Number of Auxiliary Contacts NC |
1
|
| Number of Poles |
4P
|
| Rated Operational Voltage |
Main Circuit 1000 V
|
| Rated Frequency |
Main Circuit 50 / 60 Hz
|
| Conventional Free air Thermal Current Ith |
350
|
| Rated Operational Current AC 1 Ie |
{
"1000_V_40_C": 275,
"1000_V_60_C": 250,
"1000_V_70_C": 200,
"690_V_40_C": 350,
"690_V_60_C": 300,
"690_V_70_C": 240
}
|
| Rated Operational Current AC 3 Ie |
{
"415_V_55_C": 205,
"440_V_55_C": 205,
"380_400_V_55_C": 205,
"220_230_240_V_55_C": 205
}
|
| Rated Operational Power AC 3 Pe |
{
"415_V": 110,
"440_V": 132,
"380_400_V": 110,
"220_230_240_V": 55
}
|
| Rated Breaking Capacity AC 3 |
8 x Ie AC-3
|
| Rated Breaking Capacity AC 3e |
8.5 x Ie AC-3e
|
| Rated Making Capacity AC 3 |
10 x Ie AC-3
|
| Rated Making Capacity AC 3e |
12 x Ie AC-3e
|
| Short-Circuit Protective Devices |
gG Type Fuses 400 A
|
| Rated Short-time Withstand Current Low Voltage Icw |
{
"10_s": 350,
"15_min": 947,
"1_min": 2050,
"1_s": 1640,
"30_s": 670
}
|
| Maximum Breaking Capacity |
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 3500 A
|
| Rated Insulation Voltage Ui |
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V, acc. to UL/CSA 600 V
|
| Rated Impulse Withstand Voltage Uimp |
Main Circuit 8 kV
|
| Maximum Electrical Switching Frequency |
{
"AC-1": "300 cycles per hour",
"AC-3": "300 cycles per hour"
}
|
| Mechanical Durability |
5000000
|
| Maximum Mechanical Switching Frequency |
300 cycles per hour
|
| Coil Operating Limits |
(acc. to IEC 60947-4-1) 0.85 x Uc Min. … 1.1 x Uc Max. (at θ ≤ 70 °C)
|
| Rated Control Circuit Voltage Uc |
50 Hz 100 … 250 V, 60 Hz 100 … 250 V, DC Operation 100 … 250 V
|
| Coil Consumption |
{
"Holding_at_Max_Rated_Control_Circuit_Voltage_50_Hz": "7 V·A",
"Holding_at_Max_Rated_Control_Circuit_Voltage_60_Hz": "7 V·A",
"Holding_at_Max_Rated_Control_Circuit_Voltage_DC": "2.5 W",
"Pull-in_at_Max_Rated_Control_Circuit_Voltage_50_Hz": "220 V·A",
"Pull-in_at_Max_Rated_Control_Circuit_Voltage_60_Hz": "220 V·A",
"Pull-in_at_Max_Rated_Control_Circuit_Voltage_DC": "190 W"
}
|
| Power Loss |
at Rated Operating Conditions per Pole 25 W
|
| Operate Time |
{
"Between_Coil_De-energization_and_NO_Contact_Opening": "45 … 80 ms",
"Between_Coil_Energization_and_NO_Contact_Closing": "25 … 60 ms"
}
|
| Connecting Capacity Main Circuit |
{
"Flexible": "2 x 50 … 95 mm²",
"Rigid_Al-Cable": "1 x 95 … 185 mm²",
"Rigid_Cu-Cable_1": "1 x 6 … 150 mm²",
"Rigid_Cu-Cable_2": "2 x 50 … 120 mm²"
}
|
| Connecting Capacity Auxiliary Circuit |
{
"Flexible_with_Ferrule": "2x 0.75 … 2.5 mm²",
"Flexible_with_Insulated_Ferrule": "2x 0.75 … 2.5 mm²",
"Flexible": "2×0.75 … 2.5 mm²",
"Solid": "2 x 1 … 4 mm²",
"Stranded": "2 x 1 …. 4 mm²"
}
|
| Degree of Protection |
{
"Auxiliary_Terminals": "IP40",
"Coil_Terminals": "IP20",
"Main_Terminals": "IP00"
}
|
| Tightening Torque |
{
"Cable_Lug": "9 N·m",
"Main_Circuit": "14 … 31 N·m"
}
|
| Terminal Type |
Main Circuit: Bars
|
| Product Main Type |
Block Contactor
|
| Maximum Operating Voltage UL CSA |
Main Circuit 600 V
|
| General Use Rating UL CSA |
(1000 V AC) 275 A
|
| Horsepower Rating UL CSA |
{
"200_208_V_AC_Three_Phase": "30 Hp",
"200_V_AC_Three_Phase": "60 hp",
"208_V_AC_Three_Phase": "60 hp",
"220_240_V_AC_Three_Phase": "30 Hp",
"220_240_V_AC_Three_Phase_75_hp": "75 hp",
"440_480_V_AC_Three_Phase": "75 Hp",
"440_480_V_AC_Three_Phase_150_hp": "150 hp",
"550_600_V_AC_Three_Phase": "100 Hp",
"550_600_V_AC_Three_Phase_200_hp": "200 hp"
}
|
| Ambient Air Temperature |
{
"With_Thermal_O_L_Relay": "-25 … 50 °C",
"Without_Thermal_O_L_Relay": "-40 … 70 °C",
"For_Storage": "-40 … 70 °C"
}
|
| Maximum Operating Altitude Permissible |
3000
|
| Conflict Minerals Reporting Template |
Available
|
| REACH Declaration |
Available
|
| RoHS Declaration |
Available
|
| RoHS Information |
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
|
| Toxic Substances Control Act TSCA |
Available
|
| WEEE B2C B2B |
Business To Business
|
| WEEE Category |
5. Small Equipment (No External Dimension More Than 50 cm)
|
| ABB EcoSolutions |
Yes
|
| ABB Site Meeting Group Waste To Landfill Target |
Non-hazardous waste is sent to a landfill, where there is no alternative option available within 100km of a facility
|
| End Of Life Disassembling Instructions |
Available
|
| Environmental Product Declaration EPD |
Available
|
| Improved Energy Efficiency for Customers |
Product requires less energy to operate compared to similar product on market or older products from the same line
|
| Recyclability Rate of the Product acc EN45555 |
79.2 %
|
| Sustainable Material Content in Product wt |
{
"Recycled_Metal": "35 %"
}
|
| Certificates and Declarations |
{
"ABS_Certificate": "Available",
"BV_Certificate": "Available",
"CB_Certificate": "Available",
"CQC_Certificate": "Available",
"Declaration_of_Conformity_CCC": "Available",
"Declaration_of_Conformity_CE": "Available",
"Declaration_of_Conformity_UKCA": "Available",
"EAC_Certificate": "Available",
"LR_Certificate": "Available",
"PRS_Certificate": "Available",
"RINA_Certificate": "Available",
"RMRS_Certificate": "Available",
"UL_Certificate": "Available"
}
|
| Package Level 1 Units |
box 1 piece
|
| Package Level 1 Width |
16.6
|
| Package Level 1 Depth Length |
23.8
|
| Package Level 1 Height |
18
|
| Package Level 1 Gross Weight |
3.9
|
| Package Level 1 EAN |
7320500503706
|
| Object Classification Code |
Q
|
| ETIM 7 |
EC000066 – Power contactor, AC switching
|
| ETIM 8 |
EC000066 – Power contactor, AC switching
|
| ETIM 9 |
EC000066 – Power contactor, AC switching
|
| eClass |
V11.0 : 27371003
|
| UNSPSC |
39121529
|
| IDEA Granular Category Code IGCC |
4758 >> Iec Contactors
|
| E Number Finland |
3707214
|
| E Number Norway |
4117785
|
| E Number Sweden |
3210335
|