Description
AF30-30-00-12 Contactor
Product ID: 1SBL277001R1200
EAN: 3471523111226
Description: 3 pole – 690 V IEC or 600 UL contactor with screw terminals, controlling motors up to 15 kW / 400 V AC (AC-3) or 20 hp / 480 V UL and switching power circuits up to 50 A (AC-1) or 50 A UL general use. AF technology with wide control voltage range 48-130 V 50/60 Hz and DC, managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Built-in surge protection for a compact solution. Block type design, easily extended with add-on auxiliary contact blocks and a wide range of accessories.
Dimensions (cm): Width: 4.5, Depth: 8.6, Height: 8.6
Weight (kg): 0.31
Electrical Ratings and Technical Specifications:
Rated operational voltage (main circuit): 690 V
Rated frequency (control circuit): 50 / 60 Hz
Thermal current Ith: 50 A at 40 °C
Operational current AC-1: 50 A (40 °C), 42 A (60 °C), 37 A (70 °C)
Operational current AC-3: 32 A (415 V 60 °C), 32 A (440 V 60 °C), 28 A (500 V 60 °C), 21 A (690 V 60 °C), 32 A (380/400 V 60 °C), 33 A (220/230/240 V 60 °C)
Operational current DC-1: up to 50 A depending on voltage and poles configuration
Rated operational power AC-3: 15 kW (400 V), 18.5 kW (440-690 V), 15 kW (380/400 V), 9 kW (220/230/240 V)
Short-time withstand current (Icw): 350 A (10 s), 50 A (15 min), 150 A (1 min), 700 A (1 s), 225 A (30 s)
Breaking capacity: 500 A at 440 V, 200 A at 690 V
Rated insulation voltage: 690 V IEC, 600 V UL/CSA
Impulse withstand voltage: 6 kV
Max electrical switching frequency: 600 cycles/hr (AC-1), 150 cycles/hr (AC-2/AC-4), 1200 cycles/hr (AC-3)
Max mechanical switching frequency: 3600 cycles/hr
Rated control circuit voltage: 48-130 V AC/DC at 50/60 Hz
Power loss per pole: 2.4 W (AC-1), 0.9 W (AC-3)
Operating times: De-energization to NC closing: 13-98 ms, De-energization to NO opening: 11-95 ms, Energization to NC opening: 38-90 ms, Energization to NO closing: 40-95 ms
Mounting: DIN rail TH35-15 or TH35-7.5 acc. to IEC 60715, or 2 x M4 screws diagonally
Connection capacity main circuit: flexible ferrule 1.5-10 mm², insulated ferrule 1.5-10 mm², rigid solid 2.5-4 mm², rigid stranded 2.5-10 mm²
Connection capacity control circuit: flexible ferrule 0.75-2.5 mm², insulated ferrule 0.75-2.5 mm², rigid solid 1-2.5 mm², rigid stranded 1-2.5 mm²
Wire stripping length: control circuit 10 mm, main circuit 14 mm
Degree of protection: Coil terminals IP20, Main terminals IP20 acc. to IEC 60529, IEC 60947-1, EN 60529
Tightening torque: control circuit 1.2 N·m, main circuit 2.5 N·m
Terminal type: Screw terminals
UL/CSA max operating voltage: 600 V
UL/CSA ratings: General use 50 A at 600 V AC
Horsepower rating UL/CSA: 2 hp single phase 120 V AC, up to 25 hp three phase 550-600 V AC
Environmental ratings: Ambient temperature -25 to 60 °C with thermal overload relay, -40 to 70 °C without, storage -60 to +80 °C
Climatic withstand per IEC standards, max altitude 3000 m
Resistance to shock and vibration per IEC 60068 standards
Pollution degree: 3