Description
Product AF30-30-00-14 Contactor
Type and Identification: The AF30-30-00-14 is a 3 pole, block contactor designed for 690 V IEC or 600 V UL applications with screw terminals.
Functionality: It controls motors up to 15 kW at 400 V AC (AC-3) or 20 hp at 480 V UL and switches power circuits up to 50 A (AC-1) or 50 A UL general use. Utilizing AF technology, it supports a wide control voltage range of 250-500 V at 50/60 Hz and DC, managing large control voltage variations for reduced panel energy consumption and distinct operation in unstable networks. Built-in surge protection offers a compact solution.
Design and Extensions: AF contactors have a block type design and can be extended with add-on auxiliary contact blocks and a wide range of accessories.
Dimensions: Width 4.5 cm, Depth 8.6 cm, Height 8.6 cm.
Weight: 0.35 kg.
Technical Details: It has 3 normally open main contacts and no normally closed or auxiliary contacts. Adheres to IEC/EN 60947-1 and IEC/EN 60947-4-1 standards plus UL and CSA certifications.
Rated Voltages and Currents: Main circuit voltage up to 690 V, control circuit operates at 50 / 60 Hz. Thermal current is 50 A at 40 °C. Operational currents vary with temperature and voltage; for example, AC-1 operational current rated 50 A at 690 V at 40 °C.
Power Ratings: Rated operational power up to 15 kW at 400 V AC (AC-3), with variations depending on voltage.
Durability: Maximum short-time withstand current 350 A for 10 seconds at 40 °C; breaking capacity of 500 A at 440 V and 200 A at 690 V.
Electrical Characteristics: Rated insulation voltage 690 V per IEC, impulse withstand voltage 6 kV, electrical switching frequency max 600 cycles/hour (AC-1), mechanical switching frequency max 3600 cycles/hour.
Control Circuit Voltage: Compatible control voltages include 250 to 500 V at 50 Hz, 60 Hz and DC.
Power loss: 2.4 W per pole at AC-1 conditions, 0.9 W per pole at AC-3 conditions.
Operate Times: Between coil de-energization and NC closing: 13-98 ms; coil energization and NO closing: 40-95 ms.
Mounting: Suitable for DIN rails TH35-15 and TH35-7.5 according to IEC 60715 and mounting by 2 diagonal M4 screws.
Terminals: Screw terminals; tightening torque 1.2 N·m for control circuit, 2.5 N·m for main circuit. Wire stripping length is 10 mm for control circuit and 14 mm for main circuit.
UL/CSA Ratings: Max voltage 600 V, general use rating 50 A, various horsepower ratings for single and three phase motors.
Environmental Conditions: Operating temperature range is -25 to 60 °C with thermal overload relay, -40 to 70 °C without, and storage from -60 to 80 °C. Max altitude without derating is 3000 m. Climatic withstand per IEC 60068-2-30 and 60068-2-11.
Protection Class: Coil and main terminals have IP20 degree of protection.
Compliance: RoHS, REACH, conflict minerals reporting, and multiple certificates including UL, CSA, CB, CCC, CQC, DNV, KC, LR, RINA, RMRS, ABS, BV, and more.