Description
AF370-40-11-13 Block Contactor by ABB
The AF370-40-11-13 is a 4 pole contactor designed for 1000 V IEC or 600 V UL applications. It features pre-mounted auxiliary contacts and Main Circuit Bars, capable of controlling motors up to 200 kW at 400 V AC (AC-3) and switching power circuits up to 525 A (AC-1) or 420 A for UL general use. Thanks to AF technology, it offers a wide control voltage range of 100-250 V at 50/60 Hz and DC, effectively managing large control voltage variations, reducing panel energy consumption, and ensuring distinct operations in unstable networks. Surge protection is integrated, providing a compact, reliable solution.
The contactor has a block type design and is easily extendable with add-on auxiliary contact blocks and a wide range of accessories. It includes a mounting kit with all necessary screws, washers, sockets for terminal connections, and mounting screws.
Dimensions and Weight
Net Width: 18.4 cm, Net Depth/Length: 18 cm, Net Height: 22.5 cm, Net Weight: 5.7 kg.
Electrical Characteristics
Main Contacts: 4 NO, 0 NC.
Auxiliary Contacts: 1 NO, 1 NC.
Rated Operational Voltage: 1000 V main circuit.
Rated Frequency: 50 / 60 Hz.
Thermal Current (Ith): 525 A.
Rated Operational Currents AC-1: 400 A at 1000 V and 40 °C, varying with temperature down to 290 A at 70 °C; up to 525 A at 690 V and 40 °C.
Rated Operational Current AC-3: 370 A at 55 °C.
Rated Power AC-3: 200 kW at 380-440 V, 110 kW at 220-240 V.
Breaking Capacity and Making Capacity follow 8x and 10x Ie ratings respectively, with enhanced AC-3e capacities up to 12x Ie.
Short-Circuit Protective Devices: gG Type Fuses 630 A.
Short-time Withstand Current (Icw): from 600 A for 10s up to 3700 A for 1 min at 40 °C.
Max Breaking Capacity: 5000 A at 440 V with cos phi specifications 0.45 or 0.35.
Insulation and Durability
Rated insulation voltage per IEC and VDE: 1000 V, UL/CSA: 600 V.
Impulse Withstand Voltage: 8 kV.
Mechanical Durability: 5 million operations.
Maximum Mechanical Switching Frequency: 300 cycles per hour.
Electrical Switching Frequency: 300 cycles per hour for AC-1 and AC-3.
Control Circuit and Coil
Control Voltage Range: 100 to 250 V at 50 Hz, 60 Hz, and DC.
Coil Consumption: Holding 17.5 V·A at 50/60 Hz and 4.5 W at DC; Pull-in values up to 410 V·A/W.
Operating limits at 0.85 to 1.1 times the rated control voltage at temperatures up to 70 °C.
Connecting Capacity
Main Circuit: Flexible cables 2 x 70 to 185 mm²; rigid aluminum cables 1 x 185 to 240 mm²; rigid copper cables 1 x 6 to 300 mm² or 2 x 70 to 185 mm².
Auxiliary Circuit: Flexible with ferrule 1x or 2x 0.75 to 2.5 mm²; solid and stranded wires from 1 to 4 mm².
Degree of Protection
Auxiliary Terminals: IP40, Coil Terminals: IP20, Main Terminals: IP00.
Tightening Torque: Cable lug 9 N·m, main circuit terminals 22 to 43 N·m.
Terminal Type: Bars.
UL/CSA Ratings
Max Operating Voltage UL/CSA: 600 V.
General Use Rating: 520 A at 1000 V AC.
Horsepower Ratings vary by voltage and phase, e.g., 50 Hp at 200-208 V AC, up to 350 Hp at 550-600 V AC.
Environmental Specifications
Operating ambient temperature ranges from -25 to 55 °C depending on configuration; storage up to -40 to 70 °C.
Maximum operating altitude: 3000 m without derating.
Compliance and Certification
Customs Tariff Code: 85364900.
Conflict Minerals, REACH, RoHS compliant.
Multiple certificates including UL, ABS, BV, CB, CQC, CE, UKCA, EAC, LR, PRS, RINA, RMRS.
WEEE Category 5: Small Equipment with no external dimension over 50 cm.
EcoSolutions approved with 76.3% recyclability rate per EN45555.
Design incorporates recycled metal content of 33% weight.