| Weight | 11.544 kg |
|---|
| Dimensions | 30 × 39.5 × 27.5 cm |
|---|
| Product Title | variable speed drive, Altivar 212, 15kW, 20hp, 480V, 3 phases, with EMC, IP21 |
|---|
| Model | ATV212HD15N4 |
|---|
| Product Range | Altivar 212 Variable Frequency Drive VFD |
|---|
| Device Short Name | ATV212 |
|---|
| Product Destination | Asynchronous motors |
|---|
| Phase | 3 |
|---|
| Motor Power kW | 15 |
|---|
| Maximum Horse Power Rating hp | 20 |
|---|
| Supply Voltage Limits V | 323…528 |
|---|
| Supply Frequency Hz | 50…60 (±5%) |
|---|
| Line Current A 480V | 22.8 |
|---|
| Line Current A 380V | 28.5 |
|---|
| Range of Product | Altivar 212 |
|---|
| Product or Component Type | Variable speed drive |
|---|
| Product Specific Application | Pumps and fans in HVAC |
|---|
| Communication Port Protocol | [
"BACnet",
"Modbus",
"METASYS N2",
"APOGEE FLN",
"LonWorks"
] |
|---|
| Rated Supply Voltage V | 380…480 (±15/10%) |
|---|
| EMC Filter | Class C2 EMC filter integrated |
|---|
| IP Degree of Protection | IP21 |
|---|
| Apparent Power kVA 380V | 23.2 |
|---|
| Continuous Output Current A 380V | 30.5 |
|---|
| Continuous Output Current A 460V | 30.5 |
|---|
| Maximum Transient Current A | 33.6 |
|---|
| Speed Drive Output Frequency Hz | 0.5…200 |
|---|
| Speed Range | 1…10 |
|---|
| Speed Accuracy Percent | 10 |
|---|
| Local Signalling | 1 LED (red) for DC bus energized |
|---|
| Output Voltage | <= power supply voltage |
|---|
| Isolation | Electrical between power and control |
|---|
| Type of Cable | Without mounting kit 1 IEC cable 45 °C, copper 90 °C / XLPE/EPR; Without mounting kit 1 IEC cable 45 °C, copper 70 °C / PVC; With UL Type 1 kit 3 UL 508 cable 40 °C, copper 75 °C / PVC |
|---|
| Electrical Connection | VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES terminal 2.5 mm² / AWG 14; L1/R, L2/S, L3/T terminal 25 mm² / AWG 3 |
|---|
| Tightening Torque Nm VIA to RES | 0.6 |
|---|
| Tightening Torque Nm L1 to L3 | 4.5 |
|---|
| Supply Internal for Reference Potentiometer | 10.5 V DC ±5%, <10 A overload and short-circuit protection |
|---|
| Supply Internal 24VDC | 21…27 V, <200 A overload and short-circuit protection |
|---|
| Sampling Duration ms | {
"F_discrete": 2,
"R_discrete": 2,
"RES_discrete": 2,
"VIA_analog": 3.5,
"VIB_analog": 22
} |
|---|
| Response Time ms | {
"FM_analog": 2,
"FLA_FLC_discrete": 7,
"FLB_FLC_discrete": 7,
"RY_RC_discrete": 7
} |
|---|
| Accuracy Percent | {
"VIA": 0.6,
"VIB": 0.6,
"FM": 1
} |
|---|
| Linearity Error Percent | {
"VIA": 0.15,
"VIB": 0.15,
"FM": 0.2
} |
|---|
| Analogue Output Type | FM switch-configurable voltage 0…10 V DC 7620 Ohm 10 bits; FM switch-configurable current 0…20 mA 970 Ohm 10 bits |
|---|
| Discrete Output Type | Configurable relay logic FLA, FLC NO – 100000 cycles; Configurable relay logic FLB, FLC NC – 100000 cycles; Configurable relay logic RY, RC NO – 100000 cycles |
|---|
| Minimum Switching Current mA | 3 |
|---|
| Maximum Switching Current A | {
"AC_250V_resistive": 5,
"DC_30V_resistive": 5,
"AC_250V_inductive": 2,
"DC_30V_inductive": 2
} |
|---|
| Discrete Input Type | F, R, RES programmable 24 V DC level 1 PLC 4700 Ohm |
|---|
| Discrete Input Logic | Positive logic (source) F, R, RES ≤ 5 V, ≥ 11 V; Negative logic (sink) F, R, RES ≥ 16 V, ≤ 10 V |
|---|
| Dielectric Strength VDC | {
"Earth_to_power_terminals": 3535,
"Control_to_power_terminals": 5092
} |
|---|
| Insulation Resistance mOhm | ≥ 1 at 500 V DC for 1 minute |
|---|
| Frequency Resolution | {
"Display_Unit_Hz": 0.1,
"Analog_Input": "0.024/50"
} |
|---|
| Communication Service | Timeout setting 0.1 to 100 s; Read device identification (43); Monitoring inhibitable; Write single register (06); Write multiple registers (16) 2 words max; Read holding registers (03) 2 words max |
|---|
| Option Card | Communication card LonWorks |
|---|
| Power Dissipation W | 625 |
|---|
| Air Flow m3 per h | 206 |
|---|
| Functionality | Mid |
|---|
| Specific Application | HVAC |
|---|
| Variable Speed Drive Application Selection | Building – HVAC compressor for scroll; Building – HVAC fan; Building – HVAC pump |
|---|
| Motor Power Range kW 380 to 440V 3 phase | 15…25 |
|---|
| Motor Power Range kW 480 to 500V 3 phase | 15…25 |
|---|
| Motor Starter Type | Variable speed drive |
|---|
| Discrete Output Number | 2 |
|---|
| Analogue Input Number | 2 |
|---|
| Analogue Input Type | VIA switch-configurable voltage 0…10 V DC 24 V max 30000 Ohm 10 bits; VIB configurable voltage 0…10 V DC 24 V max 30000 Ohm 10 bits; VIB configurable PTC probe 0…6 probes 1500 Ohm; VIA switch-configurable current 0…20 mA 250 Ohm 10 bits |
|---|
| Analogue Output Number | 1 |
|---|
| Physical Interface | 2-wire RS 485 |
|---|
| Connector Type | 1 open style; 1 RJ45 |
|---|
| Transmission Rate bps | 9600 or 19200 |
|---|
| Transmission Frame | RTU |
|---|
| Number of Addresses | 1…247 |
|---|
| Data Format | 8 bits, 1 stop, odd even or no configurable parity |
|---|
| Type of Polarization | No impedance |
|---|
| Asynchronous Motor Control Profile | Flux vector control without sensor standard; Voltage/frequency ratio 2 points, automatic IR compensation, Energy Saving quadratic U/f, 5 points |
|---|
| Torque Accuracy Percent | 15 |
|---|
| Transient Overtorque Percent | 120 |
|---|
| Acceleration and Deceleration Ramps s | 0.01 to 3200 separately adjustable, automatic based on load |
|---|
| Motor Slip Compensation | Automatic whatever the load; Not available in voltage/frequency ratio motor control; Adjustable |
|---|
| Switching Frequency kHz | 6 to 16 adjustable; 12 to 16 with derating |
|---|
| Nominal Switching Frequency kHz | 12 |
|---|
| Braking to Standstill | By DC injection |
|---|
| Network Frequency Hz | 47.5 to 63 |
|---|
| Prospective Line Isc kA | 22 |
|---|
| Protection Type | Various thermal, short-circuit, overcurrent, overvoltage protections for drive and motor including PTC probes |
|---|
| Pollution Degree | 2 IEC 61800-5-1 |
|---|
| IP Degree Upper Part | IP20 without blanking plate on cover IEC 61800-5-1 and IEC 60529; IP21 IEC 61800-5-1 and IEC 60529; IP41 on upper part IEC 61800-5-1 and IEC 60529 |
|---|
| Vibration Resistance | 1.5 mm (3 to 13 Hz) IEC 60068-2-6; 1 gn (13 to 200 Hz) EN/IEC 60068-2-8 |
|---|
| Shock Resistance | 15 gn 11 ms IEC 60068-2-27 |
|---|
| Environmental Characteristic | Classes 3C1 and 3S2 IEC 60721-3-3 |
|---|
| Noise Level dB | 54 |
|---|
| Operating Altitude ft m | 3280.84 to 9842.52 ft (1000 to 3000 m), limited to 2000 m for Corner Grounded network with 1% derating per 100 m; ≤ 3280.84 ft (1000 m) without derating |
|---|
| Relative Humidity Percent | 5 to 95 without condensation and without dripping water IEC 60068-2-3 |
|---|
| Ambient Air Temperature Operation C | -10 to 40 (without derating); 40 to 50 with derating |
|---|
| Operating Position | Vertical ± 10 degrees |
|---|
| Product Certifications | [
"CSA",
"UL",
"C-tick",
"NOM 117"
] |
|---|
| Marking | CE |
|---|
| Standards | [
"IEC 61800-3 category C2",
"EN 61800-3 category C3",
"IEC 61800-5-1",
"UL Type 1",
"Other IEC 61800-3 environments categories C1, C2, C3"
] |
|---|
| Assembly Style | With heat sink |
|---|
| Electromagnetic Compatibility | Tested to IEC 61000-4 series for immunity and emissions |
|---|
| Regulation Loop | Adjustable PI regulator |
|---|
| Ambient Air Temperature Storage C | -25 to 70 |
|---|
| Category | US1CP4D22157 |
|---|
| Discount Schedule | CP4D |
|---|
| Returnability | Yes |
|---|
| Unit Type of Package 1 | PCE |
|---|
| Number of Units in Package 1 | 1 |
|---|
| Unit Type of Package 2 | P06 |
|---|
| Number of Units in Package 2 | 4 |
|---|
| Warranty | 18 months |
|---|
| Customs Tariff Code | US1CP4D22157 |
|---|