Product Name: Block Contactor AX09-30-10-80
Description: AX09…AX25 contactors are mainly used for controlling 3-phase motors and power circuits up to 690 V AC. These contactors are of the block type design with 3 main poles and 1 built-in auxiliary contact, AC operated control circuit, and add-on auxiliary contact blocks for front or side mounting with a wide range of accessories.
Dimensions: Width: 4.4 cm, Depth: 7.4 cm, Height: 7.4 cm
Weight: 0.326 kg
Electrical Ratings:
Main and Auxiliary Circuit Rated Operational Voltage: 690 V
Rated Frequency: 50 / 60 Hz
Conventional Free-air Thermal Current (Ith): 24 A (IEC 60947-4-1), 16 A (IEC 60947-5-1)
Rated Operational Current AC-1: 22 A at 220-240 V (55 °C), 22 A at 690 V (40 °C), 18 A at 690 V (70 °C)
Rated Operational Current AC-3: 9 A at 415-500 V (55 °C), 7 A at 690 V (55 °C)
Rated Operational Current AC-15: 2 A at 500-690 V, 6 A at 24 / 127 V, 4 A at 220 / 240 V, 3 A at 380 / 400 V
Rated Operational Current DC-13: 6 A at 24 V, 1.1 A at 110-125 V, 0.55 A at 220-250 V, 2.8 A at 400 V, 2 A at 500 V
Rated Operational Power AC-3: 2.2 kW at 220-240 V, 4 kW at 380-440 V, 5.5 kW at 500-690 V
Short-time Withstand Current: 100 A (10 s), 26 A (15 min), 50 A (1 min), 250 A (1 s), 60 A (30 s), 140 A (0.1 s)
Maximum Breaking Capacity: 250 A at 440 V, 90 A at 690 V
Rated Insulation Voltage: 690 V (IEC 60947-4-1 and VDE 0110 Gr. C)
Rated Impulse Withstand Voltage: 6 kV (Auxiliary Circuit)
Switching Frequency: Electrical: 600 cycles/h (AC-1), 1200 cycles/h (AC-15, AC-3), 900 cycles/h (DC-13), Mechanical: 3600 cycles/h
Control Circuit Voltage: 220-230 V at 50 Hz, 230-240 V at 60 Hz
Power Loss: 0.8 W (AC-1 per pole), 0.1 W (AC-3 per pole)
Operate Time: Between coil de-energization and NC contact closing: 9-16 ms; Between coil de-energization and NO contact opening: 4-11 ms; Between coil energization and NC contact opening: 7-21 ms; Between coil energization and NO contact closing: 10-26 ms
Degree of Protection: IP20 for auxiliary terminals, coil terminals and main terminals (IEC 60529, IEC 60947-1, EN 60529)
Tightening Torque: 1 N·m for auxiliary, control and main circuits
Terminal Type: Screw Terminals
UL/CSA Ratings: General use 21 A at 600 V AC; Horsepower ratings from 1/2 hp (120 V AC single phase) up to 7.5 hp (550-600 V AC three phase)
Environmental Conditions: Ambient temperature near contactor with thermal overload relay: -25 to 55 °C; without thermal overload relay: -40 to 70 °C; storage: -60 to 80 °C; operation in free air: -40 to 70 °C
Climatic Withstand: According to IEC 60068-2-30 and 60068-2-11 – UTE C 63-100 Specification II
Maximum Operating Altitude: 3000 m without derating