Description
AX12-30-10-80 Block Contactor by ABB
AX09…AX25 contactors are mainly used for controlling 3-phase motors and power circuits up to 690 V AC. These contactors are of the block type design with: – 3 main poles and 1 built-in auxiliary contact – control circuit: AC operated – add-on auxiliary contact blocks for front or side mounting and a wide range of accessories.
Product ID: 1SBL911074R8010
EAN: 3471522393807
Minimum Order Quantity: 1 piece
Dimensions: Width 4.4 cm, Depth/Length 7.4 cm, Height 7.4 cm
Net Weight: 0.326 kg
Main Contacts NO: 3, Main Contacts NC: 0, Auxiliary Contacts NO: 1, Auxiliary Contacts NC: 0
Rated Operational Voltage: Auxiliary Circuit 690 V, Main Circuit 690 V
Rated Frequency: Auxiliary Circuit 50 / 60 Hz, Main Circuit 50 / 60 Hz
Thermal Current (Ith): 26 A (IEC 60947-4-1), 16 A (IEC 60947-5-1) at 40 °C
Operational Current AC-1: 22 A (220/240 V 55°C), 25 A (690 V 40°C), 18 A (690 V 70°C)
Operational Current AC-3: 12 A (415 V 55°C), 9 A (440 V 55°C), 9 A (500 V 55°C), 7 A (690 V 55°C), 12 A (380/400 V 55°C), 12 A (220/230/240 V 55°C)
Operational Current AC-15: 2 A (500 V), 6 A (24/127 V), 4 A (220/240 V), 3 A (380/400 V), 2 A (400/440 V)
Operational Current DC-13: 6 A (24 V), 1.1 A (110/125 V), 0.55 A (220/250 V), 2.8 A (400 V), 2 A (500 V)
Operational Power AC-3: 5.5 kW (415 V), 4 kW (440 V), 5.5 kW (500 V), 5.5 kW (690 V), 5.5 kW (380/400 V), 3 kW (220/230/240 V)
Short-time Withstand Current Icw: 120 A (10 s), 26 A (15 min), 55 A (1 min), 280 A (1 s), 70 A (30 s), 140 A (0.1 s), 100 A (1 s) at 40 °C
Maximum Breaking Capacity: 250 A at 440 V, 90 A at 690 V (cos phi=0.45; 0.35 for Ie > 100 A)
Insulation Voltage (Ui): 690 V (IEC 60947-4-1 and VDE 0110 Gr. C)
Impulse Withstand Voltage (Uimp): 6 kV (Auxiliary Circuit)
Max Electrical Switching Frequency: 600 cycles/hour (AC-1), 1200 cycles/hour (AC-15, AC-3), 900 cycles/hour (DC-13)
Max Mechanical Switching Frequency: 3600 cycles/hour
Control Circuit Voltage (Uc): 50 Hz: 220-230 V, 60 Hz: 230-240 V
Power Loss: 0.8 W per pole (AC-1), 0.1 W per pole (AC-3)
Operate Times: Coil De-energization to NC Contact Closing 9-16 ms, Coil De-energization to NO Contact Opening 4-11 ms, Coil Energization to NC Contact Opening 7-21 ms, Coil Energization to NO Contact Closing 10-26 ms
Degree of Protection: IP20 (Auxiliary Terminals, Coil Terminals, Main Terminals per IEC 60529, IEC 60947-1, EN 60529)
Tightening Torque: 1 N·m (Auxiliary, Control, Main Circuits)
Terminal Type: Screw Terminals
UL/CSA Ratings: 25 A at 600 V AC general use; Horsepower rating: 3/4 hp (120 V AC single phase), up to 10 hp (550-600 V AC three phase); Full load amps for motor use range from 9.6 A to 13.8 A depending on voltage and phase
Ambient Air Temperature: With Thermal O/L Relay: -25 to 55 °C; Without Relay: -40 to 70 °C; Storage: -60 to +80 °C; Operation in Free Air: -40 to 70 °C
Climatic Withstand: IEC 60068-2-30 and 60068-2-11 – UTE C 63-100 Specification II
Maximum Operating Altitude: 3000 m without derating
Package Dimensions and Weight: Width 4.8 cm, Depth/Length 7.8 cm, Height 7.9 cm, Gross Weight 0.34 kg; Packaged as 1 piece per box
Customs Tariff Code: 85364900