AX65-30-00-80 Contactor by ABB
Description: AX50…AX80 contactors are mainly used for controlling 3-phase motors and power circuits up to 690 V AC. These contactors are of the block type design with: – 3 main poles – control circuit: AC operated – add-on auxiliary contact blocks (optional) for side mounting and a wide range of accessories.
Catalog Description: AX65-30-00-80 220-230V50Hz/230-240V60Hz Contactor
Dimensions (cm): Width: 7, Depth/Length: 11, Height: 10.8
Weight (kg): 1.01
Electrical Ratings: Rated Operational Voltage Auxiliary Circuit: 690 V, Main Circuit: 690 V; Rated Frequency: 50 / 60 Hz; Conventional Free-air Thermal Current (Ith): 125 A.
Rated Operational Current AC-1: 95 A at 220/240 V (55 °C), 115 A at 690 V (40 °C), 80 A at 690 V (70 °C). Rated Operational Current AC-3: ranges from 43 A to 65 A depending on voltage and conditions.
Rated Operational Power AC-3: Up to 37 kW at voltages 415 V to 690 V; 30 kW at 380/400 V; 18.5 kW at 220/230/240 V.
Withstand and Breaking Capacities: Short-time withstand currents from 135 A (15 min) to 1000 A (1 s) at 40 °C. Maximum breaking capacity: 1300 A at 440 V, 630 A at 690 V.
Insulation and Protection: Rated Insulation Voltage: 690 V; Impulse Withstand Voltage Auxiliary Circuit: 6 kV; Degree of Protection: Coil terminals IP20, Main terminals IP10.
Mechanical and Electrical Switching Frequencies: Electrical maximum 600 cycles/hour (AC-1 and AC-3), Mechanical max 3600 cycles/hour.
Control Circuit Voltage: 220…230 V at 50 Hz, 230…240 V at 60 Hz.
Power Loss: 6.5 W per pole at AC-1 conditions, 1.5 W per pole at AC-3 conditions.
Operate Times (ms): Various timings between coil energization/de-energization and contact opening/closing from 4 to 27 ms.
Tightening Torques (Nm): Control circuit 1 N·m, Main circuit 4 N·m; Terminal type: Screw Terminals.
UL/CSA Ratings: General use rating 90 A at 600 V AC; Horsepower ratings vary by voltage and phase up to 75 hp; Various tightening torques in in·lb; Full load amps motor use detailed by voltage/phase.
Environmental: Ambient air temperatures range from -60 to +80 °C depending on condition; Climatic withstand per IEC standards; Maximum operating altitude 3000 m without derating.
Packaging: Box dimensions 10.2 cm x 14.3 cm x 15.2 cm; Gross weight 1.12 kg.
Customs Tariff Code: 85364900