Description
Product: Circuit breaker, ComPacT NSX100F, 36kA/415VAC, 3 poles, TMD trip unit 80A
This ComPacT NSX100F is a complete 3 poles 3D fixed circuit breaker designed to optimize space and breaking capacity. It is an optimal choice for all standard and specific applications. The breaking capacity (Icu) is 36 kiloamperes rms at 415 volts AC 50/60 Hz. The operational voltage is 690 volts AC 50/60 Hz. This product embeds an 80 ampere rating thermal-magnetic trip unit (TMD). The TMD trip unit provides an adjustable thermal overload protection and a fixed magnetic protection. This 3 poles version with dimensions 10.5 cm x 16.1 cm x 8.6 cm comes with a variety of optional functions and accessories. It is compliant with international standards IEC 60947, CCC, EAC and marine specifications. ComPacT NSX100F is part of Schneider Electric EcoStruxure Power architecture.
Range: ComPacT
Device Short Name: NSX100F
Application: Distribution
Poles Description: 3P
Protected Poles Description: 3D
Rated current: 80 A at 40 °C
Rated operational voltage: 690 V AC 50/60 Hz
Network type: AC
Network frequency: 50/60 Hz
Suitability for isolation: Yes conforming to EN/IEC 60947-2
Utilisation category: Category A
Breaking capacities: 85 kA Icu at 220/240 V AC 50/60 Hz, 36 kA Icu at 380/415 V AC 50/60 Hz, 35 kA Icu at 440 V AC 50/60 Hz, 25 kA Icu at 500 V AC 50/60 Hz, 22 kA Icu at 525 V AC 50/60 Hz, 8 kA Icu at 660/690 V AC 50/60 Hz, 85 kA Icu at 240 V AC 50/60 Hz (UL), 25 kA Icu at 480 V AC 50/60 Hz (UL), 10 kA Icu at 600 V AC 50/60 Hz (UL)
Breaking capacity code: F 36 kA 415 V AC
Trip unit name: TM-D
Trip unit technology: Thermal-magnetic
Trip unit protection functions: LI
Control type: Toggle
Mounting: Fixed
Rated insulation voltage (Ui): 800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp): 8 kV
Rated service breaking capacity: 85 kA at 220/240 V AC 50/60 Hz, 36 kA at 380/415 V AC 50/60 Hz, 35 kA at 440 V AC 50/60 Hz, 12 kA at 500 V AC 50/60 Hz, 11 kA at 525 V AC 50/60 Hz, 4 kA at 660/690 V AC 50/60 Hz
Mechanical durability: 50000 cycles
Electrical durability: 50000 cycles at 440 V In/2, 30000 cycles at 440 V In, 20000 cycles at 690 V In/2, 10000 cycles at 690 V In
Power dissipation per pole: 8.77 W
Mounting support: Backplate
Mounting position: Horizontal and vertical, flat on the back
Connection: Front upside and downside
Connection pitch: 3.5 cm
Protection type: L : for overload protection (thermal), I : for short-circuit protection (magnetic)
Trip unit rating: 80 A at 40 °C
Long-time pick-up adjustment type Ir: Adjustable
Long-time protection pick-up adjustment range: 0.7…1 x In
Long-time protection delay adjustment type tr: Fixed
Long-time delay adjustment range: 120…400 s at 1.5 x In, 15 s at 6 x Ir
Instantaneous protection pick-up adjustment type Ii: Fixed
Instantaneous protection pick-up adjustment range: 640 A
Earth-leakage protection: Without
Number of slots: 5
Dimensions (W x H x D): 10.5 cm x 16.1 cm x 8.6 cm
Net weight: 2.05 kg
Standards: EN/IEC 60947-2
Overvoltage category: III
Electrical shock protection class: Class II on front face
Pollution degree: 3 conforming to IEC 60664-1
IP degree of protection: IP40 conforming to IEC 60529
IK degree of protection: IK07 conforming to IEC 62262
Operating ambient temperature: -25…70 °C
Storage ambient temperature: -50…85 °C
Relative humidity: 0…95 %
Operating altitude: 0…2000 m without derating, 2000 m…5000 m with derating
Package 1 dimensions (H x W x L): 14.0 cm x 11.0 cm x 19.5 cm
Package 1 weight: 1.786 kg
Package 2 dimensions (H x W x L): 30.0 cm x 30.0 cm x 40.0 cm
Package 2 weight: 12.874 kg
Warranty: 18 months
Customs Tariff Code: 85362090