Description
Product Name
Circuit breaker ComPacT NSX160F, 36kA at 415VAC, TMD trip unit 160A, 4 poles 4d
General Information
Range: ComPacT NSX, new generation. Circuit-breakers, to protect lines up to 630 amps. Poles description: 4P, Protected poles description: 4D, Neutral position: Left. Rated current: 160 A at 40 °C. Rated operational voltage: 690 V AC 50/60 Hz. Network type: AC. Network frequency: 50/60 Hz. Suitability for isolation: Yes conforming to EN/IEC 60947-2. Utilisation category: Category A. Trip unit name: TM-D. Trip unit technology: Thermal-magnetic. Trip unit protection functions: LI. Control type: Toggle. Circuit breaker mounting mode: Fixed.
Breaking Capacities
85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2.
36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2.
35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2.
30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2.
22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2.
8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2.
85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1.
35 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1.
10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1.
Breaking capacity code: F 36 kA 415 V AC.
Main Ratings
Rated insulation voltage: 800 V AC 50/60 Hz.
Rated impulse withstand voltage: 8 kV.
Rated service breaking capacity matches the above IEC ratings.
Mechanical durability: 40000 cycles.
Electrical durability: 40000 cycles at 440 V In/2, 20000 cycles at 440 V In, 15000 cycles at 690 V In/2, 7500 cycles at 690 V In.
Power dissipation per pole: 13.95 W.
Mounting support: Backplate.
Mounting position: Horizontal and vertical, flat on the back.
Upside connection: Front.
Downside connection: Front.
Connection pitch: 3.5 cm.
Protection type: L for overload protection (thermal), I for short-circuit protection (magnetic).
Trip unit rating: 160 A at 40 °C.
Long-time pick-up adjustment type Ir (thermal protection): Adjustable.
Long-time protection pick-up adjustment range: 0.7…1 x In.
Long-time protection delay adjustment type tr: Fixed.
Long-time delay adjustment range: 120…400 s at 1.5 x In, 15 s at 6 x Ir.
Neutral protection setting: 1 x Ir (4D).
Instantaneous protection pick-up adjustment type Ii: Fixed.
Instantaneous protection pick-up adjustment range: 1250 A.
Earth-leakage protection: Without.
Number of slots: 5.
Dimensions and Weight
Width: 14 cm.
Height: 16.1 cm.
Depth: 8.6 cm.
Net weight: 2.6 kg.
Standards and Environmental Data
Standards: EN/IEC 60947-2.
Overvoltage category: III.
Electrical shock protection class: Class II on front face.
Pollution degree: 3 conforming to IEC 60664-1.
IP degree of protection: IP40 conforming to IEC 60529.
IK degree of protection: IK07 conforming to IEC 62262.
Ambient air temperature for operation: -25…70 °C.
Ambient air temperature for storage: -50…85 °C.
Relative humidity: 0…95 %.
Operating altitude: 0 to 2000 m without derating, 2000 to 5000 m with derating.
Packing Units
Package type 1: PCE, Quantity: 1, Dimensions (HxWxL): 14 cm x 14.5 cm x 19 cm, Weight: 2.338 kg.
Package type 2: S03, Quantity: 6, Dimensions (HxWxL): 30 cm x 30 cm x 40 cm, Weight: 14.427 kg.
Warranty: 18 months.
Customs Tariff Code
85362010