Description
G12E3F80 – Circuit breaker, GoPact MCCB 125, 3 poles, 15kA at 415VAC, 80A rating, TMD trip unit, fixed thermal protection
This product is part of the new GoPact Molded Case Circuit Breakers range (MCCB). It is a complete 3 poles circuit breaker made of a 125A breaker frame and of a thermal magnetic trip unit (TMD). GoPact MCCB has a good price-performance ratio for basic applications and delivers a reliable electrical protection for your applications.
The breaking capacity (Icu) is 15kA rms at 415VAC 50/60Hz. The operational voltage is 415VAC 50/60Hz. This product embeds a 80A rating (In) thermal-magnetic trip unit (TMD). This TMD trip unit provides a fixed thermal protection Ir (against overloads) set to 1xIn (80A). And it provides a fixed magnetic (against short-circuits) protection set to 10xIn (800A).
GoPact MCCB comes with a variety of optional accessories simple to choose and to install. Product dimensions are 7.5 cm (Width) x 13 cm (Height) x 6 cm (Depth). The weight is 0.7 kg. GoPact MCCB 125 is IEC 60947-1 and IEC 60947-2 certified. GoPact MCCB range benefits from Schneider Electric quality assurance.
Specifications:
Range of product: GoPact MCCB
Product or component type: Circuit breaker
Device application: Distribution
Poles description: 3P
Protected poles description: 3D
Rated current (In): 80 A at 40 °C
Rated operational voltage (Ue): 415 V AC 50/60 Hz conforming to EN/IEC 60947-2
Suitability for isolation: Yes conforming to EN/IEC 60947-2
Utilisation category: Category A
Rated ultimate short-circuit breaking capacity (Icu): 15 kA Icu at 380/415 V AC 50/60 Hz, 25 kA Icu at 220/230 V AC 50/60 Hz conforming to EN/IEC 60947-2
Performance level: E 15 kA 380/415 V AC
Trip unit name: TM-D
Trip unit technology: Thermal-magnetic
Trip unit protection functions: LI
Control type: Toggle
Circuit breaker mounting mode: Fixed
Main electrical characteristics:
Rated insulation voltage (Ui): 440 V AC conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp): 6 kV conforming to EN/IEC 60947-2
Rated service short-circuit breaking capacity (Ics): 15 kA at 380/415 V AC 50/60 Hz, 25 kA at 220/230 V AC 50/60 Hz conforming to EN/IEC 60947-2
Mechanical durability: 30000 cycles
Electrical durability: 8000 cycles at 415 V In
Power dissipation per pole: 18.7 W
Mounting and connection:
Mounting support: Backplate
Mounting position: Horizontal and vertical, flat on the back
Upside connection: Front
Downside connection: Front
Connection terminals: screw terminals
Connection pitch: 2.5 cm
Protection and adjustment:
Protection type: L : for overload protection (thermal), I : for short-circuit protection (magnetic)
Trip unit rating: 80 A at 40 °C
Long-time pick-up adjustment type Ir (thermal protection): Fixed
Long-time protection pick-up adjustment range: 1 x In
Long-time protection delay adjustment type tr: Fixed
Instantaneous protection pick-up adjustment type Ii: Fixed
Instantaneous protection pick-up adjustment range: 10 x In
Dimensions and weight:
Width: 7.5 cm
Height: 13 cm
Depth: 6 cm
Net weight: 0.7 kg
Color: Grey (RAL 7035)
Standards and ratings:
Standards: EN/IEC 60947-1, EN/IEC 60947-2, EN/IEC 60947-2 Annex H
Overvoltage category: III
Pollution degree: 3 conforming to IEC 60664-1
IP degree of protection: IP20 conforming to IEC 60529
Ambient air temperature for operation: -20…55 °C
Ambient air temperature for storage: -35…85 °C
Operating altitude: 0…2000 m without derating, 2000…5000 m with derating
Customs Tariff Code: 85362010