Description
EasyPact CVS – CVS100F circuit breaker – 3P/3d
Product Name: EasyPact CVS
Product Code: LV510803
Type: Circuit breaker
Device Application: Distribution
Poles Description: 3P
Protected Poles Description: 3D
Earth Leakage Protection: Without
Rated Current: 25 A at 50 °C
Network Type: AC
Utilisation Category: Category A
Breaking Capacity: 36 kA Icu at 440 V AC 50/60 Hz, 36 kA Icu at 380/415 V AC 50/60 Hz, 70 kA Icu at 220/240 V AC 50/60 Hz
Trip Unit Name: TM-D
Trip Unit Technology: Thermal-magnetic
Trip Unit Rating: 25 A at 50 °C
Protection Type: Short-circuit protection (magnetic), Overload protection (thermal)
Rated Impulse Withstand Voltage: 8 kV conforming to EN/IEC 60947-2
Network Frequency: 50/60 Hz
Breaking Capacity Code: F
Rated Service Breaking Capacity: 18 kA at 440 V AC 50/60 Hz, 36 kA at 380/415 V AC 50/60 Hz, 70 kA at 220/240 V AC 50/60 Hz
Mechanical Durability: 30000 cycles
Electrical Durability: 12000 cycles 415 V In conforming to IEC 60947-2
Control Type: Toggle
Long Time Pick-up Adjustment Type Ir: Adjustable
Long Time Pick-up Adjustment Range: 0.7…1 x In
Long Time Delay Adjustment Type: Fixed
Short-time Delay Adjustment Type: Fixed
Instantaneous Pick-up Adjustment Type Ii: Fixed
Instantaneous Pick-up Adjustment Range: 300 A
Contact Position Indicator: Yes
Mounting Support: Backplate
Mounting Mode: Fixed
Upside Connection: Front
Downside Connection: Front
Connection Pitch: 3.5 cm
Compatibility Code: CVS100
Width: 10.5 cm
Depth: 8.6 cm
Height: 16.1 cm
Net Weight: 1.5 kg
Standards: EN 60947-2, IEC 60947-2
Product Certifications: GOST, IEC
Electrical Shock Protection Class: Class II
Ambient Air Temperature for Operation: -25 to 70 °C
Ambient Air Temperature for Storage: -50 to 85 °C
Unit Type of Package 1: PCE
Number of Units in Package 1: 1
Package 1 Weight: 1.773 kg
Warranty: 18 months
Customs Tariff Code: 85362000
Environmental Sustainability: Packaging made with recycled cardboard minimum 70% content. Compliant with EU RoHS Directive with exemptions and REACh regulation declaration. No specific recycling operations needed at end of life. Not included in take-back program.