Description
EasyPact CVS – CVS100B circuit breaker – 4P/4d
Product Name: EasyPact CVS
Device Short Name: CVS100B
Product Type: Circuit breaker
Device Application: Distribution
Poles Description: 4P
Protected Poles Description: 4D
Earth Leakage Protection: Without
Rated Current: 63 A at 50 °C
Network Type: AC
Utilisation Category: Category A
Breaking Capacity (Icu): 40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
Trip Unit Name: TM-D
Trip Unit Technology: Thermal-magnetic
Trip Unit Rating: 63 A at 50 °C
Protection Type: Overload protection (thermal), Short-circuit protection (magnetic)
Rated Impulse Withstand Voltage (Uimp): 8 kV conforming to EN/IEC 60947-2
Network Frequency: 50/60 Hz
Breaking Capacity Code: B
Rated Service Breaking Capacity (Ics): 15 kA at 440 V AC 50/60 Hz, 25 kA at 380/415 V AC 50/60 Hz, 40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
Neutral Position: Left
Mechanical Durability: 30000 cycles
Electrical Durability: 12000 cycles 415 V In conforming to IEC 60947-2
Control Type: Toggle
Neutral Protection Setting: 1 x Ir (4D)
Long Time Pick-up Adjustment Type Ir: Adjustable
Long Time Pick-up Adjustment Range: 0.7 to 1 x In
Long Time Delay Adjustment Type: Fixed
Short-time Delay Adjustment Type: Fixed
Instantaneous Pick-up Adjustment Type Ii: Fixed
Instantaneous Pick-up Adjustment Range: 500 A
Contact Position Indicator: Yes
Mounting Support: Backplate
Mounting Mode: Fixed
Upside Connection: Front
Downside Connection: Front
Connection Pitch: 3.5 cm
Compatibility Code: CVS100
Width: 14 cm
Depth: 8.6 cm
Height: 16.1 cm
Net Weight: 1.9 kg
Standards: IEC 60947-2, EN 60947-2
Product Certifications: GOST, IEC
Electrical Shock Protection Class: Class II
Ambient Air Temperature for Operation: -25 to 70 °C
Ambient Air Temperature for Storage: -50 to 85 °C
Unit Type of Package 1: PCE
Number of Units in Package 1: 1
Package 1 Weight: 2.209 kg
Warranty: 18 months
Customs Tariff Code: 85362000