Description
Product Name: EasyPact CVS
Device short name: CVS400N
Type: Circuit breaker, suitable for distribution applications
Poles: 3P; Protected poles: 3D
Earth leakage protection: Without
Rated current: 400 A at 50 °C
Network type: AC
Utilisation category: Category A
Breaking capacity (Icu): 70 kA at 220/240 V AC 50/60 Hz according to IEC 60947-2; 50 kA at 380/415 V AC 50/60 Hz; 42 kA at 440 V AC 50/60 Hz
Trip unit name: TM-D (Thermal-magnetic)
Trip unit rating: 400 A at 40 °C
Protection type: Overload protection (thermal) and short-circuit protection (magnetic)
Rated impulse withstand voltage (Uimp): 8 kV according to EN/IEC 60947-2
Network frequency: 50/60 Hz
Breaking capacity code: N
Rated service breaking capacity (Ics): 70 kA at 220/240 V AC; 50 kA at 380/415 V AC; 32 kA at 440 V AC
Mechanical durability: 15000 cycles
Electrical durability: 6000 cycles at 415 V according to IEC 60947-2
Control type: Toggle
Long time pick-up adjustment type Ir: Adjustable
Long time pick-up adjustment range: 0.7 to 1 times In
Long time delay adjustment type: Fixed
Short-time delay adjustment type: Fixed
Instantaneous pick-up adjustment type Ii: Adjustable
Instantaneous pick-up adjustment range: 5 to 10 times In
Contact position indicator: Yes
Mounting support: Backplate
Mounting mode: Fixed
Connections: Front for both upside and downside
Connection pitch: 4.5 cm
Compatibility code: CVS400
Dimensions (W x D x H): 14 cm x 11 cm x 25.5 cm
Standards: EN 60947-2; IEC 60947-2
Product certifications: IEC; GOST
Electrical shock protection class: Class II
Ambient air temperature for operation: -25 to 70 °C
Ambient air temperature for storage: -50 to 85 °C
Packaging: Unit type PCE with dimensions 16 cm x 16 cm x 29 cm and weight 5.8 kg. Outer pack unit P12 with 90 units, dimensions 100 cm x 80 cm x 120 cm and weight 468 kg
Warranty: 18 months
Customs Tariff Code: 85362010