Description
Product Name: Easypact CVS – CVS250B circuit breaker – 4P/4d
Product ID: LV525617
Range Name: EasyPact CVS
Device Short Name: CVS250B
Type: Circuit breaker for Distribution
Poles: 4P with 4D protected poles
Earth Leakage Protection: Without
Rated Current [In]: 200 A at 50 °C
Network Type: AC
Utilisation Category: Category A
Breaking Capacity [Icu]: 40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
Trip Unit Name and Technology: TM-D, Thermal-magnetic
Trip Unit Rating: 200 A at 40 °C
Protection Type: Overload protection (thermal), Short-circuit protection (magnetic)
Rated Impulse Withstand Voltage [Uimp]: 8 kV conforming to EN/IEC 60947-2
Network Frequency: 50/60 Hz
Breaking Capacity Code: B
Rated Service Breaking Capacity [Ics]: 15 kA at 440 V AC 50/60 Hz, 25 kA at 380/415 V AC 50/60 Hz, 40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
Neutral Position: Left
Mechanical Durability: 20000 cycles
Electrical Durability: 10000 cycles at 415 V In conforming to IEC 60947-2
Control Type: Toggle
Neutral Protection Setting: 1 x Ir (4D)
Long Time Pick-up Adjustment Type (Ir): Adjustable
Long Time Pick-up Adjustment Range: 0.7 to 1 x In
Long Time Delay Adjustment Type: Fixed
Short Time Delay Adjustment Type: Fixed
Instantaneous Pick-up Adjustment Type (Ii): Fixed
Instantaneous Pick-up Adjustment Range: 2000 A
Contact Position Indicator: Yes
Mounting Support: Backplate
Mounting Mode: Fixed
Upside Connection: Front
Downside Connection: Front
Connection Pitch: 3.5 cm
Dimensions (WxDxH): 14.0 cm x 8.6 cm x 16.1 cm
Net Weight: 2.2 kg
Standards: EN 60947-2, IEC 60947-2
Certifications: GOST, IEC
Electrical Shock Protection Class: Class II
Operation Temperature Range: -25 to 70 °C
Storage Temperature Range: -50 to 85 °C
Packaging: 1 PCE, 2.209 kg
Warranty: 18 months
Customs Tariff Code: 85362090