Description
Product Name: Easypact CVS CVS250F circuit breaker 3P/3d
Range: EasyPact CVS
Device Short Name: CVS250F
Type: Circuit breaker for Distribution with 3 poles (3P) and 3 protected poles (3D)
Earth Leakage Protection: Without
Rated Current: 200 A at 50 °C
Network Type: AC
Utilisation Category: Category A
Breaking Capacity (Icu): 36 kA at 440 V AC 50/60 Hz, 36 kA at 380/415 V AC 50/60 Hz, 70 kA at 220/240 V AC 50/60 Hz according to IEC 60947-2
Trip Unit: TM-D thermal-magnetic rated 200 A at 40 °C
Protection Type: Overload protection (thermal), Short-circuit protection (magnetic)
Rated Impulse Withstand Voltage (Uimp): 8 kV conforming to EN/IEC 60947-2
Frequency: 50/60 Hz
Breaking Capacity Code: F
Rated Service Breaking Capacity (Ics): 18 kA at 440 V AC, 36 kA at 380/415 V AC, 70 kA at 220/240 V AC per IEC 60947-2
Mechanical Durability: 20,000 cycles
Electrical Durability: 10,000 cycles at 415 V In per IEC 60947-2
Control Type: Toggle
Adjustments: Long time pick-up adjustable from 0.7 to 1 x In, Fixed long time delay, Fixed short-time delay, Fixed instantaneous pick-up up to 2000 A
Contact Position Indicator: Yes
Mounting: Backplate, Fixed mode
Connections: Front upside and downside, connection pitch 3.5 cm
Compatibility Code: CVS250
Dimensions: Width 10.5 cm, Depth 8.6 cm, Height 16.1 cm
Net Weight: 1.7 kg
Standards: EN 60947-2, IEC 60947-2
Product Certifications: GOST, IEC
Electrical Shock Protection Class: Class II
Operating Ambient Temperature: -25 to 70 °C
Storage Ambient Temperature: -50 to 85 °C
Packaging: Unit type PCE, 1 unit per package, package weight 1.773 kg with minimum 70% recycled cardboard content
Warranty: 18 months
Customs Tariff Code: 85362040
Environmental Note: Total lifecycle carbon footprint 270 CO2 equivalent emissions; complies with EU RoHS Directive with exemptions; no global take-back program participation
Description: This device is a 3 poles 3d fixed circuit breaker with a high level of performance and cost-saving functionality. It is an optimal choice for small and medium-sized buildings protection applications. The breaking capacity (Icu) is 36kA rms at 415VAC 50/60Hz. It is compliant with international standards (IEC 60947, EN 60947, CCC, CB).