Description
Product Overview
Product Name: Eaton Moeller series Power Defense molded case circuit-breaker
Catalog Number: PDE11F0100TFFJ
EAN: 9010238099364
Dimensions: Length/Depth 8.8 cm, Height 14.5 cm, Width 3 cm
Weight: 0.386 kg
Compliances: RoHS conform
Certifications: IEC IEC/EN 60947
Delivery program
Circuit breaker frame type: PDE1
Amperage Rating: 100 A
Number of poles: Single-pole
Technical data – electrical
Voltage rating: 230 V – 230 V
Max. rated operation voltage Ue AC: 230 V
Rated impulse withstand voltage (Uimp) at auxiliary contacts: 6000 V
Rated impulse withstand voltage (Uimp) at main contacts: 6000 V
Rated current (Iu): 100 A
Instantaneous current setting (Ii) – min: 100 A
Instantaneous current setting (Ii) – max: 1000 A
Overload current setting (Ir) – min: 80 A
Overload current setting (Ir) – max: 100 A
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz: 18 kA
Short-circuit total breaktime: < 10 ms
Electrical connection type of main circuit: Frame clamp
Isolation: 500 V AC (between auxiliary contacts and main contacts)n300 V AC (between the auxiliary contacts)
Overvoltage category: III
Utilization category: A
Pollution degree: 3
Technical data – mechanical
Type: Circuit breaker
Release system: Thermomagnetic release
Mounting Method: Complete device in housing DIN rail (top hat rail) mounting optional Fixed
Degree of protection: IP20 (basic degree of protection, in the operating controls area) IP20
Degree of protection (IP), front side: IP40 (with insulating surround) IP66 (with door coupling rotary handle)
Shock resistance: 20 g (half-sinusoidal shock 20 ms)
Number of auxiliary contacts (change-over contacts): 0
Number of auxiliary contacts (normally closed contacts): 0
Number of auxiliary contacts (normally open contacts): 0
Number of operations per hour – max: 120
Handle type: Rocker lever
Position of connection for main current circuit: Front side
Direction of incoming supply: Vertical and 90° in all directions
Standard terminals: Box terminal
Climatic proofing: Damp heat, constant, to IEC 60068-2-78nDamp heat, cyclic, to IEC 60068-2-30
Lifespan, mechanical: 20000 operations
Design verification as per IEC/EN 61439 – technical data
Ambient operating temperature – min: -25 °C
Ambient operating temperature – max: 70 °C
Ambient storage temperature – min: -40 °C
Ambient storage temperature – max: 70 °C
Design verification as per IEC/EN 61439
10.2.2 Corrosion resistance: Meets the product standard’s requirements.
10.2.3.1 Verification of thermal stability of enclosures: Meets the product standard’s requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat: Meets the product standard’s requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects: Meets the product standard’s requirements.
10.2.4 Resistance to ultra-violet (UV) radiation: Meets the product standard’s requirements.
10.2.5 Lifting: Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact: Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions: Meets the product standard’s requirements.
10.3 Degree of protection of assemblies: Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances: Meets the product standard’s requirements.
10.5 Protection against electric shock: Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components: Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections: Is the panel builder’s responsibility.
10.8 Connections for external conductors: Is the panel builder’s responsibility.
10.9.2 Power-frequency electric strength: Is the panel builder’s responsibility.
10.9.3 Impulse withstand voltage: Is the panel builder’s responsibility.
10.9.4 Testing of enclosures made of insulating material: Is the panel builder’s responsibility.
10.10 Temperature rise: The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating: Is the panel builder’s responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility: Is the panel builder’s responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function: The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Additional information
Features: Protection unit
Functions: System and cable protection
Special features: Fixed overload releases Ir
Customs Tariff Code: 85362010