Description
Product Name
Eaton Moeller series Power Defense molded case circuit-breaker
Catalog Number
PDE13K0160TAAJ
EAN
9010238097544
Dimensions
Length/Depth: 14.5 cm
Height: 8.7 cm
Width: 8.9 cm
Weight
1.046 kg
Compliance and Certification
RoHS conform
Certifications: IEC IEC/EN 60947
Type and Frame
Circuit breaker, Frame type PDE1
Electrical Ratings
Poles: Three-pole
Amperage Rating: 160 A
Voltage rating: 220 V – 440 V
Voltage rating (DC): 250 V
Rated current (Iu): 160 A
Instantaneous current setting (Ii): 800 A – 1280 A
Overload current setting (Ir): 128 A – 160 A
Short-circuit Breaking Capacity (Ics)
At 230 V, 50/60 Hz: 65 kA
At 400/415 V, 50/60 Hz: 50 kA
At 440 V, 50/60 Hz: 26 kA
Technical Features
Release system: Thermomagnetic release
Features: Protection unit, Motor drive optional
Special features: Thermally and magnetically adjustable (calibrated at 40 °C)
Electrical connection type of main circuit: Frame clamp
Number of operations per hour – max: 120
Handle type: Rocker lever
Utilization category: A
Overvoltage category: III
Pollution degree: 3
Direction of incoming supply: Vertical and 90° in all directions
Mechanical Data
Mounting Method: DIN rail (top hat rail) mounting optional, Fixed, Complete device in housing
Degree of protection: IP2X
Position of connection for main current circuit: Front side
Lifespan (mechanical): 25000 operations
Standard terminals: Box terminal
Operating Temperatures
Ambient operating temperature: -20 °C to 70 °C
Ambient storage temperature: -20 °C to 70 °C
Design Verification (IEC/EN 61439)
Corrosion resistance, Thermal stability of enclosures, Resistance of insulating materials to normal and abnormal heat/fire effects, UV radiation resistance, Inscriptions and Clearances and creepage distances meet product standard’s requirements. Lifting and Mechanical impact do not apply as the entire switchgear must be evaluated. Protection against electric shock, Incorporation of switching devices and components do not apply and are panel builder’s responsibility along with internal electrical circuits, connections, power-frequency electric strength, impulse withstand voltage, and testing of insulating enclosures. Temperature rise calculation and short-circuit rating are panel builder’s responsibility. Electromagnetic compatibility must be observed by panel builder. Mechanical function meets requirements if instructions are observed.
Additional Information
Functions: System and cable protection
Customs Tariff Code
85362000