Name: Eaton Moeller series Power Defense molded case circuit-breaker
Catalog Number: PDE11F0080TFFJ
Model Code: PDE11F0080TFFJ
EAN: 9010238099357
Dimensions (cm): Length/Depth: 8.8, Height: 14.5, Width: 3.0
Weight (kg): 0.386
Compliance: RoHS conform
Certifications: IEC IEC/EN 60947
Delivery Program
Type: Circuit breaker
Frame type: PDE1
Poles: Single-pole
Amperage Rating: 80 A
Release system: Thermomagnetic release
Features: Protection unit
Special features: Fixed overload releases Ir
Technical Data – Electrical
Voltage rating: 230 V – 230 V
Rated impulse withstand voltage (Uimp) at auxiliary contacts: 6000 V
Rated impulse withstand voltage (Uimp) at main contacts: 6000 V
Rated current (Iu): 80 A
Instantaneous current setting (Ii) min/max: 800 A
Overload current setting (Ir) min/max: 80 A
Rated short-circuit breaking capacity Ics at 400/415 V, 50/60 Hz: 18 kA
Short-circuit total breaktime: < 10 ms
Electrical connection type of main circuit: Frame clamp
Isolation: 500 V AC (between auxiliary contacts and main contacts), 300 V AC (between the auxiliary contacts)
Number of operations per hour max: 120
Handle type: Rocker lever
Utilization category: A
Overvoltage category: III
Pollution degree: 3
Direction of incoming supply: Vertical and 90° in all directions
Technical Data – Mechanical
Mounting Method: DIN rail (top hat rail) mounting optional, Complete device in housing, Fixed
Degree of protection: IP2X, IP20 (basic degree of protection, in the operating controls area)
Degree of protection (IP), front side: IP40 (with insulating surround), IP66 (with door coupling rotary handle)
Degree of protection (terminations): IP10 (tunnel terminal), IP00 (terminations, phase isolator and band terminal)
Shock resistance: 20 g (half-sinusoidal shock 20 ms)
Number of auxiliary contacts (change-over, normally closed, normally open): 0, 0, 0
Position of connection for main current circuit: Front side
Climatic proofing: Damp heat, constant, to IEC 60068-2-78; Damp heat, cyclic, to IEC 60068-2-30
Special features: Fixed overload releases Ir
Lifespan, mechanical: 20000 operations
Terminals
Standard terminals: Box terminal
Design verification as per IEC/EN 61439 – technical data
Ambient operating temperature: min -25 °C, max 70 °C
Ambient storage temperature: min -40 °C, max 70 °C
Customs Tariff Code
85362010