Description
EZC100N1030 Circuit Breaker EasyPact EZC100N
This is a 30 A circuit breaker for EasyPact EZC100N designed for 1 pole. It operates below rated operational voltage(Ue) of 415 V AC at 50/60 Hz or 125 V DC network. The ultimate breaking capacity(Icu) varies with network conditions, with Ics equal to 50% of Icu if matching is required. This version uses a 3 poles frame with detection on all poles and is equipped with a TMD thermal-magnetic trip unit for protection. The product is compliant with IEC 60947 standard, CE certified, and validated by independent labs including KEMA, ASEFA, TUV, and third-party Tilva. Certified for pollution degree III environments per IEC 60947, the device withstands extreme atmospheric conditions.
Mounting is possible vertically or horizontally within metal enclosures and it is protected against safety risks by padlocking. The degree of protection is IP40 for direct rotary handle and IP54 for extended rotary handle. The series includes slots for auxiliary position indication or voltage release auxiliaries placed behind the front cover.
Dimensions: Width 2.5 cm, Height 13 cm, Depth 6 cm.
Specifications:
Range of product: EasyPact
Device short name: Easypact EZC100N
Device application: Distribution
Poles description: 1P
Protected poles: 1t
Network type: AC and DC
Network frequency: 50/60 Hz
Rated current In: 30 A at 40 °C
Rated insulation voltage Ui: 690 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage Uimp: 6 kV conforming to IEC 60947-2
Rated operational voltage Ue: 125 V DC and 415 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity code: N
Breaking capacity Icu: 25 kA at 110…130 V AC, 5 kA at 125 V DC 1P, 18 kA at 220…240 V AC, 2.5 kA at 380 V AC, 2.5 kA at 400…415 V AC
Rated service breaking capacity Ics: 12.5 kA at 110/130 V AC, 2.5 kA at 125 V DC, 9 kA at 220/230/240 V AC, 1.25 kA at 380 V AC, 1.25 kA at 400/415 V AC
Suitability for isolation: Yes
Utilisation category: Category A
Trip unit name: TM-D
Trip unit technology: Thermal-magnetic
Trip unit rating: 30 A at 50 °C
Protection type: Short-circuit and Overload protection
Pollution degree: 3 conforming to IEC standards
Main features include toggle control, fixed mounting mode, backplate mounting support, front upside and downside connections, mechanical durability of 13000 cycles, 2.5 cm connection pitch, positive contact local signalling, without neutral protection or earth-leakage protection.
Standards: EN/IEC 60947-2, EN/IEC 60947-1, GB/T 14048.2, JIS C8201-2-2. Protection ratings: IP20 and IK07. Operation ambient temperature from -25 to 70 °C, storage from -35 to 85 °C. Packaging details include single and bulk packaging with weights and dimensions specified.
Customs Tariff Code: 85362000