Description
EZC100N1100 – circuit breaker Easypact EZC100N – TMD – 100 A – 1 pole 1d
This is a 100A circuit breaker for EasyPact EZC100N. This product can work below rated operational voltage(Ue) 415VAC at 50/60Hz or 125VDC network. The ultimate breaking capacity(Icu) is shown differently, depended on the condition of network, Ics=50%Icu if need to match. This version of product is designed one pole frame with detection on one pole, equiped TMD trip unit for thermal-magnetic protection.
It is compliance with standard IEC60947, CE certification and some independent lab(KEMA, ASEFA, TUV) or third-party Tilva. This device is certified for operation in pollution degree III environment as defined by IEC60947, and pass the test of extremely atmospheric conditions.
Device can be mounted vertically or horizontally in a metal enclosure, and against from safety risk by padlocking. The degree of protection is IP40 for direct rotary handle, and IP54 for extended rotary handle.
This series have slots used for indication or voltage release auxiliaries positioning, depending on where it is inserted in the device behind the front cover of circuit breaker.
The fixed dimension is 2.5cm width, 13cm height, 6cm depth.
Range of product: EasyPact
Product or component type: Circuit breaker
Device short name: Easypact EZC100N
Device application: Distribution
Poles description: 1P
Protected poles description: 1t
Network type: AC and DC
Network frequency: 50/60 Hz
Rated current [In]: 100 A at 40 °C
Rated insulation voltage [Ui]: 690 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage [Uimp]: 6 kV conforming to IEC 60947-2
Rated operational voltage [Ue]: 125 V DC and 415 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity code: N
Breaking capacity Icu: 25 kA at 110-130 V AC 50/60 Hz, 5 kA at 125 V DC 1P, 18 kA at 220-240 V AC 50/60 Hz, 2.5 kA at 380 V AC 50/60 Hz, 2.5 kA at 400-415 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity [Ics]: 12.5 kA at 110/130 V AC 50/60 Hz, 2.5 kA at 125 V DC, 9 kA at 220/230/240 V AC 50/60 Hz, 1.25 kA at 380 V AC 50/60 Hz, 1.25 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
Suitability for isolation: Yes conforming to IEC 60947-2
Utilisation category: Category A
Trip unit name: TM-D
Trip unit technology: Thermal-magnetic
Protection type: Short-circuit protection and overload protection
Pollution degree: 3 conforming to IEC 60664-1 and IEC 947-1
Control type: Toggle
Mounting mode: Fixed
Mounting support: Backplate
Connections: Front upside and downside connections
Mechanical durability: 13000 cycles
Connection pitch: 25 mm
Local signalling: Positive contact indication
Neutral protection setting: Without protection
Earth-leakage protection: Without
Current sensor rating range: 100 A
Dimensions (Width x Height x Depth): 2.5 cm x 13 cm x 6 cm
Standards: JIS C8201-2-2, GB/T 14048.2, EN/IEC 60947-1, EN/IEC 60947-2
Degree of protection: IP20 under IEC 60529
Impact protection: IK07 under IEC 62262
Ambient air temperature for operation: -25 to 70 °C
Ambient air temperature for storage: -35 to 85 °C
Packaging and environmental: Packaging made with recycled cardboard, minimum 70% recycled content; compliant with EU RoHS directive; no specific recycling operations needed; not included in global take-back program; certified for polluted atmosphere operation; IP40/IP54 protection with rotary handles.