Description
LRD05 – TeSys Deca Thermal Overload Relay
Product Type: Differential thermal overload relay designed for motor protection and compatible with TeSys D contactors LC1D09, LC1D12, LC1D18, LC1D25, LC1D32, LC1D38.
Thermal Protection Adjustment Range: 0.63 to 1 A calibrated per Class 10A IEC 60947-4-1.
Electrical Ratings: Rated insulation voltage up to 600 V CSA and UL; operational voltage 690 V AC; frequency 0 to 400 Hz.
Mechanical and Installation: Mounting support includes plate, rail with specific accessories, or under the contactor.
Dimensions (cm): Height 6.6 cm, Width 4.5 cm, Depth 7.0 cm.
Weight: Net weight approximately 0.124 kg.
Connection Terminals: Control circuit screw clamp terminals for 1 to 2.5 mm² cables (flexible with or without cable end and solid), power circuit terminals for 1.5 to 10 mm² flexible without cable end, or 1 to 6 mm² solid without cable end.
Tripping Threshold: 1.14 ± 0.06 times Ir according to IEC 60947-4-1 standard.
Auxiliary Contact Composition: 1 normally open (NO) and 1 normally closed (NC) contact.
Control Type: Red push-button stop and blue push-button reset.
Environmental Resistance: IP20 protection degree, vibration resistance 6 Gn, shock resistance 15 Gn for 11 milliseconds, temperature compensation range from -20 to 60 °C, dielectric strength 1.89 kV at 50 Hz.
Packaging: Package dimensions and weights vary from single piece pack (5 x 7.8 x 8.9 cm, 139 g) to bulk packages.
Standards and Certifications: Complies with EN/IEC 60947-4-1, EN/IEC 60947-5-1, UL 60947-4-1, UL 60947-5-1, CSA, CCC, EAC, BV, RINA, DNV-GL, Lloyds register of shipping, ATEX INERIS, and UKCA certifications.
Environmental Data: Carbon footprint of 13 kg CO2 equivalent; packaging made with at least 70% recycled cardboard and free of single-use plastic; EU RoHS compliant.
Warnings: This product can expose you to chemicals including Antimony oxide & Antimony trioxide, known to cause cancer per California Proposition 65.