Description
Product Name
circuit breaker Compact NSX100F – TMD – 16 A – 3 poles 3d
Range Name
ComPact NSX – Circuit-breakers, to protect lines up to 630A
Main Specifications
Complete 3P 3d fixed circuit breaker designed to optimize space and breaking capacity. Breaking capacity (Icu) is 36 kA rms at 415 VAC 50/60 Hz. Operational voltage is 690 VAC 50/60 Hz. Embedded 16 A rating thermal-magnetic trip unit (TM-D) provides adjustable thermal overload protection and fixed magnetic protection. 3 poles version with dimensions 10.5 cm x 16.1 cm x 8.6 cm. Compliant with international standards IEC 60947, CCC, EAC and marine specifications. Part of Schneider Electric EcoStruxure Power architecture.
Electrical Characteristics
Rated current: 16 A at 40 °C. Rated ultimate short-circuit breaking capacity varies by voltage: 10 kA at 600 V AC (UL 508), 25 kA at 480 V AC (UL 508), 85 kA at 240 V AC (UL 508), 22 kA at 525 V AC, 25 kA at 500 V AC, 35 kA at 440 V AC, 36 kA at 380/415 V AC, 8 kA at 660/690 V AC, 85 kA at 220/240 V AC (IEC 60947-2 standard). Rated insulation voltage 800 V AC. Rated impulse withstand voltage 8 kV. Rated service short-circuit breaking capacity ranges from 4 kA to 85 kA depending on voltage.
Utilisation category: Category A. Control type: Toggle. Mounting mode: Fixed. Network type AC, frequency 50/60 Hz. Suitability for isolation according to EN/IEC 60947-2.
Mechanical and Dimensional Data
Mechanical durability: 50000 cycles. Electrical durability: up to 50000 cycles depending on voltage and current. Mounting support: Backplate. Connection pitch: 3.5 cm. Dimensions (WxHxD): 10.5 cm x 16.1 cm x 8.6 cm. Weight: 2.05 kg.
Protection and Adjustments
Protection type: L (overload, thermal), I (short-circuit, magnetic). Long-time protection pick-up adjustment: 0.7 to 1 times In (adjustable). Long-time protection delay: fixed 120–400 s at 1.5x In, 15 s at 6x Ir. Short-time protection pick-up fixed at 190 A and delay fixed. No earth-leakage protection.
Standards and Certifications
Standards: EN/IEC 60947. Certifications: CCC, EAC, Marine. Overvoltage category: Class II. Electrical shock protection class: Class II. Pollution degree: 3 per IEC 60664-1. IP rating IP40. IK rating IK07.
Operating Conditions
Ambient air temperature for operation: -25 to 70 °C. For storage: -50 to 85 °C. Relative humidity 0–95%. Operating altitude: 0 to 2000 m without derating, 2000 to 5000 m with derating.
Packaging
Package 1 dimensions: 14.0 cm height, 19.0 cm width, 11.8 cm length; weight 1.86 kg (1 unit). Package 2 dimensions: 30.0 cm height, 40.0 cm width, 60.0 cm length; weight 23.086 kg (12 units).
Warranty
18 months contractual warranty.