Description
MS165-54 Manual Motor Starter by ABB
Description: MS165 is a compact and powerful range for motor protection up to 45 kW (400 V) / 80 A in width of 5.5 cm. They offer reliable protection for motors in the event of overload or phase failure. The devices have trip class 10. It features a clear and reliable fault indication in a separate window for short-circuit tripping. Additional features include a built-in disconnect function, temperature compensation, trip-free mechanism, and a rotary handle with clear switch position indication. Suitable for both three- and single-phase applications. The handle is lockable to prevent unauthorized changes. Accessories such as auxiliary contacts, signaling contacts, undervoltage releases, shunt trips, and power in-feed blocks are available and compatible across MS116/MS132/MS165 range.
Electrical Ratings: Rated operational current is 54 A with setting range 40 to 54 A. Rated operational power AC-3 is 22 kW at 400 V (three phase).
Short-Circuit Capacities: Rated service short-circuit breaking capacity (Ics) includes 30 kA (230 V AC), 100 kA (250 V DC) with 3 poles in series, 30 kA (400 V AC), 30 kA (440 V AC), 20 kA (500 V AC), and 6 kA (690 V AC). Rated ultimate short-circuit breaking capacity (Icu) includes 50 kA (230 V AC), 100 kA (250 V DC), 50 kA (400 V AC), 45 kA (440 V AC), 20 kA (500 V AC), and 8 kA (690 V AC).
Dimensions and Weight: Width is 5.5 cm, height 14.265 cm, depth 12.21 cm, and weight approximately 0.97 kg.
Mounting: Suitable for mounting positions 1 to 6 on DIN rails TH35-15 and TH35-7.5 according to IEC 60715. Minimum mounting distances: Horizontal conductive board (up to 1000 V) 0.15 cm, vertical 7.5 cm; zero spacing needed horizontally between same devices and 15 cm vertically.
Terminals: Screw terminals supporting flexible with ferrule 1 to 35 mm², rigid and solid 1 to 4 mm², stranded up to 50 mm². Tightening torque is 4 N·m. Wire stripping length is 16 mm. Recommended screwdriver is Pozidriv 2.
Standards and Certifications: Complies with CSA 22.2 No. 14, IEC/EN 60947-1, -2, -4-1, UL 60947-4-1. UL short-circuit rating up to 65 kA at 480Y/277 V AC. Numerous certificates including ABS, ATEX, BV, CB, CCC, CQC, CE, UKCA, DNV GL, EAC, IECEx, KC, LR, RMRS, UL.
Environmental: Operating temperature -25 to +70 °C (compensated -25 to +60 °C), storage -50 to +80 °C. Maximum altitude 2000 m. Resistant to shocks (11 ms pulse 25g) and vibration (5g on mounting plate).
Customs Tariff Code: 85362010