Description
MS165-65 Manual Motor Starter 52 … 65 A
Manufacturer: ABB
Description: MS165 is a compact and powerful range for motor protection up to 45 kW (400 V) / 80 A in width of 5.5 cm. They offer reliable protection for motors in the event of overload or phase failure. The devices have trip class 10 and include a clear and reliable indication of fault in a separate window in case of short-circuit tripping. Features include built-in disconnect function, temperature compensation, trip-free mechanism, and a rotary handle with clear switch position indication. Suitable for three- and single phase applications. The handle is lockable to prevent unauthorized changes. Accessories such as auxiliary contacts, signaling contacts, undervoltage releases, shunt trips, and power in-feed blocks are available, compatible across MS116/MS132/MS165 range.
Dimensions: Width 5.5 cm, Height 14.265 cm, Depth 12.21 cm, Weight 0.98 kg
Electrical ratings:
Rated operational current (Ie): 65 A
Setting range: 52 … 65 A
Rated operational power AC-3: 30 kW @ 400 V three-phase
Rated insulation voltage (Ui): 1000 V
Rated impulse withstand voltage (Uimp): 8 kV
Rated frequency: 50 Hz and 60 Hz
Operating frequency range: 0 … 415 Hz
Rated service short-circuit breaking capacity (Ics): (230 V AC) 30 kA, (250 V DC) 3 poles in series 100 kA, (400 V AC) 30 kA, (440 V AC) 30 kA, (500 V AC) 20 kA, (690 V AC) 6 kA
Rated ultimate short-circuit breaking capacity (Icu): (230 V AC) 50 kA, (250 V DC) 100 kA, (400 V AC) 50 kA, (440 V AC) 45 kA, (500 V AC) 20 kA, (690 V AC) 8 kA
Rated instantaneous short-circuit current setting (Ii): 975 A
Power loss per pole: 5.14 … 8.02 W
Conventional free-air thermal current: 65 A
Number of poles: 3
Degree of protection: Housing IP20, Main circuit terminals IP10
Pollution degree: 3
Electrical durability: 25000 cycles
Mechanical durability: 50000 cycles
Terminal type: Screw terminals
Connecting capacity main circuit: Flexible with ferrule 1/2x 1 … 35 mm², flexible with insulated ferrule 1/2x 1 … 35 mm², Flexible 1/2x 1 … 35 mm², Rigid 1/2x 1 … 4 mm², Solid 1/2x 1 … 4 mm², Stranded 1/2x 1 … 50 mm²
Tightening torque: 4 N·m
Wire stripping length: 16 mm
Recommended screwdriver: Pozidriv 2
Mounting position: 1 … 6
Mounting on DIN rail: TH35-15 (35 x 15 mm) and TH35-7.5 (35 x 7.5 mm) acc. to IEC 60715
Minimum mounting distance: Electrical conductive board horizontal up to 1000 V: 0.15 cm, up to 400 V: 0 cm, up to 690 V: 0.15 cm, vertical: 7.5 cm; Other device same type horizontal: 0 cm, vertical: 15 cm
Actuator type: Rotary handle
Contact position indication: ON / OFF / TRIP
Standards: CSA 22.2 No. 14, IEC/EN 60947-1, IEC/EN 60947-2, IEC/EN 60947-4-1, UL 60947-4-1
Customs Tariff Code: 85362090