Description
Block Contactor Relay NF31E-13
The NF31E-13 is a 690 V IEC or 600 UL 4-pole contactor relay with screw terminals, used for switching auxiliary and control circuits. Thanks to the AF technology, the contactor relay has a wide control voltage range (100-250 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. NF contactor relays have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories. These contactor relays include mechanically-linked auxiliary contacts compliant with Annex L of IEC 60947-5-1 and are side-marked with the “Mechanically Linked” symbol.
Specifications:
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85364900
Dimensions (WxLxH): 4.5 cm x 7.7 cm x 8.6 cm
Weight: 0.27 kg
Number of Auxiliary Contacts (NO): 3
Number of Auxiliary Contacts (NC): 1
Number of Poles: 4
Standards: IEC/EN 60947-1, IEC/EN 60947-5-1, UL 60335-2-40 LZGH2 A2L, UL 508, CSA C22.2 No. 60335-2-40 LZGH2 A2L, CSA C22.2 No. 14-13
Rated Operational Voltage Auxiliary Circuit: 690 V
Rated Frequency: Auxiliary Circuit 50 / 60 Hz, Control Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith): 16 A (at Θ = 40 °C acc. to IEC 60947-5-1)
Rated Operational Current AC-15 (Ie): (500 V) 2 A, (690 V) 2 A, (24 / 127 V) 6 A, (220 / 240 V) 4 A, (400 / 440 V) 3 A
Rated Operational Current DC-13 (Ie): Various from 6 A at 24 V to 0.1 A at 600 V with corresponding power ratings
Rated Short-time Withstand Current Low Voltage (Icw): 140 A for 0.1 s, 100 A for 1 s
Rated Insulation Voltage (Ui): 690 V (IEC), 600 V (UL/CSA)
Rated Impulse Withstand Voltage (Uimp): 6 kV
Max Electrical Switching Frequency: 1200 cycles/hour (AC-15), 900 cycles/hour (DC-13)
Max Mechanical Switching Frequency: 6000 cycles/hour
Rated Control Circuit Voltage (Uc): 100 … 250 V at 50 Hz, 60 Hz and DC operation
Power Loss: 0.1 W at 6 A per pole
Operate Times: Various coil energization and de-energization timings within 11 ms to 98 ms range
Mounting: DIN Rail TH35-15 or TH35-7.5 per IEC 60715, or 2 x M4 screws placed diagonally
Connection Capacity: Flexible and rigid wire sizes from 0.75 to 2.5 mm² and AWG 18-14
Wire Stripping Length: 10 mm
Degree of Protection: IP20 for auxiliary and coil terminals
Tightening Torque: 1.2 N·m for auxiliary and control circuits; 11 in·lb (UL/CSA)
Environmental Conditions: Storage temp -60 to +80 °C, operation -40 to 70 °C; altitude up to 3000 m without derating
Resistance to Shock and Vibrations: Meets IEC 60068-2-27 and vibration criteria
Pollution Degree: 3
Sustainable Material Content: 86 % recycled cardboard packaging, 28 % recycled metal in product