Description
Product: PSE250-600-70 Softstarter
Long Description: Softstarter PSE250-600-70 for max 600V main voltage and 100 – 250V 50/60Hz control supply voltage.
Operational Voltage: 208 … 600 V AC
Control Supply Voltage: 100 … 250 V AC
Control Circuit Voltage: DC Operation 24 V
Frequency: 50/60 Hz
Operational Power: 75 kW (230 V), 132 kW (400 V), 160 kW (500 V)
Operational Current: 250 A
Service Factor: 100%
Overload Protection: Build-in electronic overload protection with Integrated Electronic Overload: Yes
Starting Capacity at Max Rated Current: 4 times rated current for 10s
Ramp Time: 1 to 30 seconds
Initial Voltage During Start: 30 to 70%
Current Limit Function: 1.5 to 7 times rated current
Signal Relays: Run, By-pass, Fault, Overload – all Yes
Analog Outputs: 4 to 20 mA
LED Indications: Completed Start Ramp, Ready to Start/Standby, Running R, Ramping Up/Down (Green), Protection (Yellow), Fault (Red)
Starts Per Hour: 10 at 3.5 times rated current for 7 seconds (50% ON/OFF time)
Communication: FiledBusPlug (Optional)
Degree of Protection: IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
Terminals: Main Circuit Bars; Hole Diameter 1.02 cm; Width x Thickness 2.0 cm x 0.5 cm; Control Circuit Connections Rigid 1 x 2.5 mm² or Rigid 2 x 1.5 mm²; Supply Circuit Rigid 1 x 2.5 mm²
Tightening Torque: Control Circuit 0.5 N·m; Main Circuit 28 N·m; Supply Circuit 0.5 N·m
Dimensions (WxHxD): 19.0 cm x 55.0 cm x 23.65 cm
Weight: 13.9 kg
Ambient Temperature: Operation -25 to +60 °C; Storage -40 to +70 °C
Classification Codes: ETIM 7,8,9 – EC000640 Soft starter; eClass V11.0 27370907; UNSPSC 39121521
Customs Tariff Code: 85371091