Description
Product Name: S201M-C6
Manufacturer: ABB
Product ID: 2CDS271001R0064
EAN: 4016779549967
Catalog Description: Miniature Circuit Breaker – S200M – 1P – 6 A – C – (AC) 10 kA
Description: System pro M compact S200M miniature circuit breakers are current limiting. They have two different tripping mechanisms, the delayed thermal tripping mechanism for overload protection and the electromechanic tripping mechanism for short circuit protection. Available in different characteristics (B,C,D,K,Z), configurations (1P,1P+N,2P,3P,3P+N,4P), breaking capacities (up to 10 kA at 230/400 V AC) and rated currents (up to 63A). All comply with IEC/EN 60898-1 and IEC/EN 609 47-2 for residential, commercial and industrial applications. Bottom-fitting auxiliary contact can be mounted on S200M to save 50% space.
Electrical Characteristics:
Dielectric Test Voltage: 2 kV (50/60 Hz – 1 min)
Rated Ultimate Short-Circuit Breaking Capacity at 133 V AC: 25 kA
Rated Ultimate Short-Circuit Breaking Capacity at 230 V AC: 15 kA
Rated Ultimate Short-Circuit Breaking Capacity at 400 V: 15 kA
Rated Service Short-Circuit Breaking Capacity at 133 V AC: 18.8 kA
Rated Service Short-Circuit Breaking Capacity at 230 V AC: 7.5 kA
Rated Operational Voltage: 230/400 V AC (IEC 60898-1), 230 V AC (IEC 60947-2)
Operational Voltage: max 253 V AC, max 72 V DC, min 12 V AC/DC
Rated Insulation Voltage (Ui): 440 V (IEC/EN 60664-1)
Rated Impulse Withstand Voltage (Uimp): 4 kV (at 2000 m 5 kV, at Sea Level 6.2 kV)
Input Voltage Type: AC/DC
Rated Current: 6 A
Rated Short-Circuit Capacity: 10 kA (230/400 V AC)
Rated Conditional Short-Circuit Current (Inc): 15 kA (230 V)
Frequency: 50 Hz, Rated Frequency: 50 / 60 Hz
Power Loss: 2 W per pole at rated operating conditions
Energy Limiting Class: 3
Tripping Characteristic: C
Number of Poles: 1P
Number of Protected Poles: 1
Electrical Endurance: 20000 AC cycles
Mechanical Endurance: 20000 cycles
Tightening Torque: 2.8 N·m
Actuator Type: Toggle with marking I / O, material Insulation Group II, Black, Sealable
Screw Terminal Type: Failsafe Bi-directional Cylinder-lift Terminal
Recommended Screw Driver: Pozidriv 2
Accessories Available: Yes
Connecting Capacity: Busbar 10 mm², Flexible with Ferrule 0.75 to 25 mm², Rigid 0.75 to 35 mm², Stranded 0.75 to 35 mm²
Installation Size: 1 (acc. to DIN 43880)
Terminal Type: Screw Terminals
Housing Material: Insulation Group II, RAL 7035
UL/CSA Maximum Operating Voltage: 60 V DC, 480Y/277 V AC
UL/CSA Interrupting Rating acc. to UL1077: 6 kA (277 V AC), 6 kA (480Y/277 V AC), 10 kA (60 V DC)
UL/CSA Connecting Capacity Busbar: 14-8 AWG, Conductor: 14-4 AWG
UL/CSA Tightening Torque: 18 in·lb
RoHS Declaration: Compliant with EU Directive 2011/65/EU and Amendment 2015/863 (Feb 28, 2024)
REACH Declaration: Does not contain substances above 0.1 mass % (valid until Sep 17, 2025)
Conflict Minerals Reporting: Germany
WEEE Category: 5. Small Equipment (No External Dimension More Than 50 cm)
WEEE: Business To Business
Environmental Conditions: Operating temperature -25 to +55 °C, Storage -40 to +70 °C, Reference Ambient Temperature 30 °C
Degree of Protection: IP20, IP40 enclosure with cover IP40
Pollution Degree: 3
Resistance to Vibrations: 20 cycles with load 0.8 In: 5g (5 to 150 to 5 Hz)
Resistance to Shock acc. IEC 60068-2-27: 25g (2 shocks, 13 ms)
Dimensions (cm): Width 1.75, Height 8.8, Depth 6.9
Product Net Weight: 0.112 kg, Pole Net Weight: 0.125 kg
Packaging: carton 10 piece, Gross Weight 1.16 kg
External Classifications: ETIM 9 & 10: EC000042 – Miniature circuit breaker (MCB), UNSPSC: 39121603, eClass: V11.0 : 27141901, IGCC: 4897 Miniature circuit breakers, Object Classification: F
Standards: IEC/EN 60898-1, CSA 22.2 No. 235, IEC/EN 60947-2, UL 1077
Certifications: EN, IEC