Description
S202-C63 Miniature Circuit Breaker
Type: S202-C63
Poles: 2P
Rated Current: 63 A
Tripping Characteristic: C
Breaking Capacity: (AC) 6 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu): 10 kA (125 V DC), 20 kA (230 V AC), 10 kA (400 V AC), 10 kA (440 V AC), 20 kA (48 V DC)
Rated Service Short-Circuit Breaking Capacity (Ics): 15 kA (230 V AC), 7.5 kA (400 V AC), 7.5 kA (440 V AC)
Rated Operational Voltage: 400 V AC (IEC 60898-1), 440 V AC (IEC 60947-2)
Electrical Endurance: 10000 AC cycles
Mechanical Endurance: 20000 cycles
Power Supply Connection: Arbitrary
Contact Position Indication: Red ON / Green OFF
Energy Limiting Class: 3
Tightening Torque: 2.8 N·m
Actuator Type: Toggle, Marking: I / O
Terminal Type: Screw Terminals, Failsafe Bi-directional Cylinder-lift Terminal
Connecting Capacity: Busbar 10/10 mm², Flexible 0.75 to 25 mm² with Ferrule, Rigid 0.75 to 35 mm², Stranded 0.75 to 35 mm²
Installation Size: acc. to DIN 43880 1
Wire Stripping Length: 1.25 cm
Housing Material: Insulation Group II, RAL 7035
Degree of Protection: IP20, IP40 Enclosure with Cover IP40
Operating Ambient Temperature: -25 to +55 °C
Storage Ambient Temperature: -40 to +70 °C
Reference Ambient Temperature: 30 °C
Frequency: 50 Hz, Rated Frequency 50 / 60 Hz
Rated Insulation Voltage (Ui): 440 V
Rated Impulse Withstand Voltage (Uimp): 4 kV (at 2000 m: 5 kV, at Sea Level: 6.2 kV)
Power Loss: 9.6 W total, 4.8 W per pole at rated operating conditions
Mounting Type: DIN-Rail, Mounting on TH35-15 (35 x 15 mm) and TH35-7.5 (35 x 7.5 mm) rails acc. to IEC 60715
Mounting Position: any
RoHS Compliance: Following EU Directive 2011/65/EU and Amendment 2015/863
REACH Compliance: Does not contain substances > 0.1 mass percentage
Certifications: IEC/EN 60898-1, IEC/EN 60947-2, UL 1077
Customs Tariff Code: 39121603