| Weight | 0.48 kg |
|---|
| Dimensions | 6.9 × 7 × 8.8 cm |
|---|
| Product ID | 2CDS274001R0404 |
|---|
| Catalog Description | Miniature Circuit Breaker – S200M – 4P – 40 A – C – (AC) 10 kA |
|---|
| Long Description | System pro M compact S200M miniature circuit breakers are current limiting. They have two different tripping mechanisms, the delayed thermal tripping mechanism for overload protection and the electromechanic tripping mechanism for short circuit protection. They are available in different characteristics (B,C,D,K,Z), configurations (1P,1P+N,2P,3P,3P+N,4P), breaking capacities (up to 10 kA at 230/400 V AC) and rated currents (up to 63A). All MCBs of the product range S200M comply with IEC/EN 60898-1 and IEC/EN 609 47-2, allowing the use for residential, commercial and industrial applications. Bottom-fitting auxiliary contact can be mounted on S200M to save 50% space. |
|---|
| Technical Data | {
"Dielectric_Test_Voltage_Attribute": "2 kV",
"Rated_Ultimate_Short_Circuit_Breaking_Capacity_230VAC_Attribute": 25,
"Rated_Ultimate_Short_Circuit_Breaking_Capacity_400VAC_Attribute": 15,
"Rated_Ultimate_Short_Circuit_Breaking_Capacity_440VAC_Attribute": 15,
"Rated_Service_Short_Circuit_Breaking_Capacity_230VAC_Attribute": 7.5,
"Power_Supply_Connection_Attribute": "Arbitrary",
"Contact_Position_Indication_Attribute": "Red ON / Green OFF",
"Energy_Limiting_Class_Attribute": 3,
"Electrical_Endurance_Attribute": "10000 AC cycle",
"Mechanical_Endurance_Attribute": "20000 cycle",
"Number_of_Protected_Poles_Attribute": 4,
"Number_of_Poles_Attribute": "4P",
"Tightening_Torque_Nm_Attribute": 2.8,
"Actuator_Type_Attribute": "Toggle",
"Screw_Terminal_Type_Attribute": "Failsafe Bi-directional Cylinder-lift Terminal",
"Actuator_Marking_Attribute": "I / O",
"Actuator_Material_Attribute": "Insulation Group II, Black, Sealable",
"Recommended_Screw_Driver_Attribute": "Pozidriv 2",
"Accessories_Available_Attribute": "Yes",
"Connecting_Capacity_Busbar_mm2_Attribute": 10,
"Connecting_Capacity_Flexible_Ferrule_mm2_min_Attribute": 0.75,
"Connecting_Capacity_Flexible_Ferrule_mm2_max_Attribute": 25,
"Connecting_Capacity_Rigid_mm2_min_Attribute": 0.75,
"Connecting_Capacity_Rigid_mm2_max_Attribute": 35,
"Installation_Size_DIN_43880_Attribute": 1,
"Terminal_Type_Attribute": "Screw Terminals"
} |
|---|
| Dielectric Test Voltage | 2 kV |
|---|
| Rated Ultimate Short Circuit Breaking Capacity 230VAC | 25 |
|---|
| Rated Ultimate Short Circuit Breaking Capacity 400VAC | 15 |
|---|
| Rated Ultimate Short Circuit Breaking Capacity 440VAC | 15 |
|---|
| Rated Service Short Circuit Breaking Capacity 230VAC | 7.5 |
|---|
| Power Supply Connection | Arbitrary |
|---|
| Contact Position Indication | Red ON / Green OFF |
|---|
| Energy Limiting Class | 3 |
|---|
| Electrical Endurance | 10000 AC cycle |
|---|
| Mechanical Endurance | 20000 cycle |
|---|
| Number of Protected Poles | 4 |
|---|
| Number of Poles | 4P |
|---|
| Tightening Torque Nm | 2.8 |
|---|
| Actuator Type | Toggle |
|---|
| Screw Terminal Type | Failsafe Bi-directional Cylinder-lift Terminal |
|---|
| Actuator Marking | I / O |
|---|
| Actuator Material | Insulation Group II, Black, Sealable |
|---|
| Recommended Screw Driver | Pozidriv 2 |
|---|
| Accessories Available | Yes |
|---|
| Connecting Capacity Busbar mm2 | 10 |
|---|
| Connecting Capacity Flexible Ferrule mm2 min | 0.75 |
|---|
| Connecting Capacity Flexible Ferrule mm2 max | 25 |
|---|
| Connecting Capacity Rigid mm2 min | 0.75 |
|---|
| Connecting Capacity Rigid mm2 max | 35 |
|---|
| Installation Size DIN 43880 | 1 |
|---|
| Terminal Type | Screw Terminals |
|---|
| Electrical Characteristics | {
"Tripping_Characteristic_Attribute": "C",
"Rated_Operational_Voltage_AC_Attribute": 400,
"Rated_Operational_Voltage_AC_Standard_Attribute": "IEC 60898-1 / IEC 60947-2",
"Operational_Voltage_Max_DC_Attribute": 125,
"Operational_Voltage_Max_AC_Attribute": 440,
"Operational_Voltage_Min_AC_Attribute": 12,
"Operational_Voltage_Min_DC_Attribute": 12,
"Rated_Insulation_Voltage_Ui_Attribute": 440,
"Rated_Impulse_Withstand_Voltage_Uimp_Attribute": "4 kV (standard) / 5 kV at 2000 m / 6.2 kV at sea level",
"Input_Voltage_Type_Attribute": "AC/DC",
"Rated_Current_In_Attribute": 40,
"Rated_Short_Circuit_Capacity_Attribute": "10 kA (AC) at 230 V AC",
"Rated_Conditional_Short_Circuit_Current_230V_Attribute": 15,
"Rated_Conditional_Short_Circuit_Current_400V_Attribute": 25,
"Frequency_Hz_Attribute": 50,
"Rated_Frequency_Attribute": "50 / 60 Hz",
"Power_Loss_W_total_Attribute": 19.2,
"Power_Loss_W_per_Pole_Attribute": 4.8,
"Overvoltage_Category_Attribute": "III",
"I2t_Characteristic_Attribute": "S200_S200M_S200P let-through energy B-C"
} |
|---|
| Tripping Characteristic | C |
|---|
| Rated Operational Voltage AC | 400 |
|---|
| Rated Operational Voltage AC Standard | IEC 60898-1 / IEC 60947-2 |
|---|
| Operational Voltage Max DC | 125 |
|---|
| Operational Voltage Max AC | 440 |
|---|
| Operational Voltage Min AC | 12 |
|---|
| Operational Voltage Min DC | 12 |
|---|
| Rated Insulation Voltage Ui | 440 |
|---|
| Rated Impulse Withstand Voltage Uimp | 4 kV (standard) / 5 kV at 2000 m / 6.2 kV at sea level |
|---|
| Input Voltage Type | AC/DC |
|---|
| Rated Current In | 40 |
|---|
| Rated Short Circuit Capacity | 10 kA (AC) at 230 V AC |
|---|
| Rated Conditional Short Circuit Current 230V | 15 |
|---|
| Rated Conditional Short Circuit Current 400V | 25 |
|---|
| Frequency Hz | 50 |
|---|
| Rated Frequency | 50 / 60 Hz |
|---|
| Power Loss W total | 19.2 |
|---|
| Power Loss W per Pole | 4.8 |
|---|
| Overvoltage Category | III |
|---|
| I2t Characteristic | S200_S200M_S200P let-through energy B-C |
|---|
| Mechanical Design | {
"Housing_Material_Attribute": "Insulation Group II, RAL 7035"
} |
|---|
| Housing Material | Insulation Group II, RAL 7035 |
|---|
| UL CSA Technical | {
"Maximum_Operating_Voltage_UL_CSA_DC_Attribute": 125,
"Maximum_Operating_Voltage_UL_CSA_AC_Attribute": "480Y/277 V AC",
"Interrupting_Rating_UL_1077_125V_DC_kA_Attribute": 10,
"Interrupting_Rating_UL_1077_277V_AC_kA_Attribute": 6,
"Interrupting_Rating_UL_1077_480Y_277V_AC_kA_Attribute": 6,
"Connecting_Capacity_UL_CSA_Busbar_AWG_Attribute": "14-8 AWG",
"Connecting_Capacity_UL_CSA_Conductor_AWG_Attribute": "14-4 AWG",
"Tightening_Torque_UL_CSA_in_lb_Attribute": 18
} |
|---|
| Maximum Operating Voltage UL CSA DC | 125 |
|---|
| Maximum Operating Voltage UL CSA AC | 480Y/277 V AC |
|---|
| Interrupting Rating UL 1077 125V DC kA | 10 |
|---|
| Interrupting Rating UL 1077 277V AC kA | 6 |
|---|
| Interrupting Rating UL 1077 480Y 277V AC kA | 6 |
|---|
| Connecting Capacity UL CSA Busbar AWG | 14-8 AWG |
|---|
| Connecting Capacity UL CSA Conductor AWG | 14-4 AWG |
|---|
| Tightening Torque UL CSA in lb | 18 |
|---|
| Environmental | {
"RoHS_Declaration_Attribute": "Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019",
"RoHS_Date_Attribute": "2024-02-28",
"REACH_Declaration_Attribute": "False – does not contain substances > 0.1 mass percentage",
"REACH_Date_Attribute": "2025-09-17",
"Conflict_Minerals_Reporting_Template_Attribute": "9008497a-14f6-4cfd-83c5-11cf3bc660d1 Germany",
"WEEE_Category_Attribute": "5. Small Equipment (No External Dimension More Than 50 cm)",
"WEEE_B2C_B2B_Attribute": "Business To Business",
"Ambient_Air_Temperature_Operation_C_Attribute": "-25 to +55",
"Ambient_Air_Temperature_Storage_C_Attribute": "-40 to +70",
"Reference_Ambient_Air_Temperature_C_Attribute": 30,
"Degree_of_Protection_Attribute": "IP20 / IP40 with Enclosure Cover",
"Pollution_Degree_Attribute": 3,
"Environmental_Conditions_Attribute": "28 cycles with 55 °C / 90-96 % and 25 °C / 95-100 %",
"Resistance_to_Vibrations_Attribute": "20 Cycles with Load 0.8 In: 5g 5 … 150 … 5 Hz",
"Resistance_to_Shock_IEC_60068_2_27_Attribute": "25g 2 shocks 13 ms"
} |
|---|
| RoHS Declaration | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
|---|
| RoHS Date | 2024-02-28 |
|---|
| REACH Declaration | False – does not contain substances > 0.1 mass percentage |
|---|
| REACH Date | 2025-09-17 |
|---|
| Conflict Minerals Reporting Template | 9008497a-14f6-4cfd-83c5-11cf3bc660d1 Germany |
|---|
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
|---|
| WEEE B2C B2B | Business To Business |
|---|
| Ambient Air Temperature Operation C | -25 to +55 |
|---|
| Ambient Air Temperature Storage C | -40 to +70 |
|---|
| Reference Ambient Air Temperature C | 30 |
|---|
| Degree of Protection | IP20 / IP40 with Enclosure Cover |
|---|
| Pollution Degree | 3 |
|---|
| Environmental Conditions | 28 cycles with 55 °C / 90-96 % and 25 °C / 95-100 % |
|---|
| Resistance to Vibrations | 20 Cycles with Load 0.8 In: 5g 5 … 150 … 5 Hz |
|---|
| Resistance to Shock IEC 60068 2 27 | 25g 2 shocks 13 ms |
|---|
| Dimensions | {
"Width_in_Number_of_Modular_Spacings_Attribute": 4,
"Pole_Net_Weight_kg_Attribute": 0.125,
"Built_In_Depth_cm_Attribute": 6.9
} |
|---|
| Width in Number of Modular Spacings | 4 |
|---|
| Pole Net Weight kg | 0.125 |
|---|
| Built In Depth cm | 6.9 |
|---|
| Ordering Info | {
"Package_Level_1_Units_Attribute": "carton 1 piece",
"Package_Level_1_Gross_Weight_kg_Attribute": 0.5,
"E_Number_Norway_Attribute": "1665740",
"E_Number_Sweden_Attribute": "2101268"
} |
|---|
| Package Level 1 Units | carton 1 piece |
|---|
| Package Level 1 Gross Weight kg | 0.5 |
|---|
| E Number Norway | 1665740 |
|---|
| E Number Sweden | 2101268 |
|---|
| Certifications and Standards | {
"Declaration_of_Conformity_CE_Attribute": "EU Declaration of Conformity S200L, S200, S200M",
"Declaration_of_Conformity_UKCA_Attribute": "UKCA Declaration of Conformity – S200, S200M",
"ETIM_9_Attribute": "EC000042 – Miniature circuit breaker (MCB)",
"ETIM_10_Attribute": "EC000042 – Miniature circuit breaker (MCB)",
"UNSPSC_Attribute": 39121603,
"eClass_Attribute": "V11.0 : 27141901",
"IDEA_Granular_Category_Code_IGCC_Attribute": "4897 >> Miniature circuit breakers",
"Object_Classification_Code_Attribute": "F",
"Standards_Attribute": [
"IEC/EN 60898-1",
"CSA 22.2 No. 235",
"IEC/EN 60947-2",
"UL 1077"
],
"Certification_Agency_Attribute": [
"EN",
"IEC"
],
"Standardization_Body_Attribute": [
"EN",
"IEC"
],
"Customs_Tariff_Code_Attribute": "39121603"
} |
|---|
| Declaration of Conformity CE | EU Declaration of Conformity S200L, S200, S200M |
|---|
| Declaration of Conformity UKCA | UKCA Declaration of Conformity – S200, S200M |
|---|
| ETIM 9 | EC000042 – Miniature circuit breaker (MCB) |
|---|
| ETIM 10 | EC000042 – Miniature circuit breaker (MCB) |
|---|
| UNSPSC | 39121603 |
|---|
| eClass | V11.0 : 27141901 |
|---|
| IDEA Granular Category Code IGCC | 4897 >> Miniature circuit breakers |
|---|
| Object Classification Code | F |
|---|
| Standards | [
"IEC/EN 60898-1",
"CSA 22.2 No. 235",
"IEC/EN 60947-2",
"UL 1077"
] |
|---|
| Certification Agency | [
"EN",
"IEC"
] |
|---|
| Standardization Body | [
"EN",
"IEC"
] |
|---|
| Customs Tariff Code | 39121603 |
|---|
| Installation | {
"Instructions_and_Manuals_Attribute": "S200, S300 instruction manual",
"Mounting_on_DIN_Rail_Attribute": "TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715, TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715",
"Mounting_Position_Attribute": "any"
} |
|---|
| Instructions and Manuals | S200, S300 instruction manual |
|---|
| Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715, TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 |
|---|
| Mounting Position | any |
|---|