Description
TA25DU-4.0M Thermal Overload Relay
Manufacturer: ABB
Product ID: 1SAZ211201R2033
EAN: 4013614482502
Description: TA25DU-4.0M (2.8-4.0A) thermal overload relay is an economic electromechanical protection device for the main circuit. It offers reliable and fast protection for motors in the event of overload or phase failure. The device has trip class 10A. Further features include temperature compensation, trip contact (NC), signal contact (NO), automatic or manual reset selectable, trip-free mechanism, STOP and Test function, and trip indication. The overload relays connect directly to the block contactors. Single mounting kits are available as accessory.
Customs Tariff Code: 85364900
Minimum Order Quantity: 1 piece
Dimensions (WxHxD): 4.4 cm x 8.0 cm x 9.4 cm
Net Weight: 0.15 kg
Rated Operational Voltage: Main Circuit 690 V AC, Main Circuit 440 V DC
Rated Operational Current (Ie): 4 A
Rated Frequency: Auxiliary Circuit 50 Hz/60 Hz/DC, Main Circuit 50 Hz/60 Hz/DC
Number of Poles: 3P
Number of Auxiliary Contacts: NC: 1, NO: 1
Number of Protected Poles: 3
Conventional Free-air Thermal Current (Ith): Auxiliary Circuit NC 5 A, NO 5 A
Rated Operational Current AC-15: Various according to voltage, e.g. (120 V) NC 3 A, NO 1.5 A
Degree of Protection: Housing IP20, Main Circuit Terminals IP10
Pollution Degree: 3
Connecting Capacity Auxiliary Circuit: Flexible 0.75 … 2.5 mm², Rigid 0.75 … 4 mm²
Connecting Capacity Main Circuit: Flexible with Ferrule 0.75 … 4 mm², Flexible 0.75 … 4 mm², Rigid 0.75 … 4 mm²
Recommended Screw Driver: Auxiliary Circuit: Pozidriv 1, Main Circuit: Pozidriv 2
Power Loss at Rated Conditions per Pole: 1.1 … 2.2 W
Suitable For: AX09, AX12, AX18, AX25, AX32, AX40
Standards: CSA 22.2 No. 14, IEC/EN 60947-1, IEC/EN 60947-4-1, IEC/EN 60947-5-1, UL 508
Max Operating Voltage UL/CSA: Main Circuit 600 V AC
Contact Rating UL/CSA: NC: B600, NO: C600
Connecting Capacity UL/CSA Main Circuit: Flexible 16-8 AWG, Stranded 16-8 AWG
Connecting Capacity UL/CSA Auxiliary Circuit: Flexible 18-14 AWG, Stranded 18-14 AWG
Tightening Torque UL/CSA: Auxiliary Circuit 12 in·lb, Main Circuit 12 in·lb
Ambient Air Temperature: Operation -25 … +55 °C, Compensated -25 … +55 °C, Storage -40 … +70 °C
Maximum Operating Altitude Permissible: 2000 m
Resistance to Shock acc. to IEC 60068-2-27: 25g 2 shocks 13 ms
RoHS Information: Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
WEEE Category: 5. Small Equipment (No External Dimension More Than 50 cm)
Certificates: CB, CCC, CCS, CQC, CE, EAC, RMRS, UL
Package Level 1: Box 1 piece, Dimensions 9.8 cm x 8.2 cm x 4.7 cm, Gross Weight 0.17 kg, EAN: 4013614482502
Package Level 2: 36 pieces, Dimensions 23.0 cm x 31.0 cm x 38.0 cm, Gross Weight 10.946 kg
Classification Codes: ETIM 9 and 10: EC000106 – Thermal overload relay, eClass V11.0: 27371501, UNSPSC: 39121520, IDEA Granular: 5364 >> Overload relay, E-Number Finland: 3707399