Description
XT1N 160 TMD 125-1250 4p F F InN=100%
Manufacturer: ABB
Product Name: Moulded Case Circuit Breaker
Product Type: Automatic Circuit Breaker
Extended Product Type: XT1N 160 TMD 125-1250 4p F F InN=100%
Long Description: C.BREAKER TMAX XT1N 160 FIXED FOUR-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMD R 125-1250 A FULLY RATED NEUTRAL
Product ID: 1SDA067427R1
EAN: 8015644013219
Order Code US and Canada: XT1NE4125AFF000XXX
E-Number (Norway): 4379238
E-Number (Sweden): 3182422
Minimum Order Quantity: 1 piece
Customs Tariff Number: 85362090
Dimensions (cm): Width: 10.16, Height: 13, Depth/Length: 7
Net Weight (kg): 1.4
Package Dimensions Level 1 (cm): Width: 12.8, Height: 13.5, Depth/Length: 14.3
Package Gross Weight Level 1 (kg): 1.47
Circuit Breaker Type to be Associated: Power Distribution
Product Main Type: SACE Tmax XT
Version: F
Connecting Capacity Main Circuit: Busbar 45.5 … 80 mm²
Current Type: AC/DC
Electrical Durability: 8000 cycles
Mechanical Durability: 25000 cycles
Number of Poles: 4P
Opening Time: CB with SOR 30 ms / CB with UVR 30 ms
Power Loss at Rated Operating Conditions per Pole: 10.7 W
Rated Current (In): 125 A
Rated Frequency (f): 50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp): 8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii): 1250 A
Rated Insulation Voltage (Ui): 800 V
Rated Operational Voltage: 690 V AC / 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics): Various values up to 50 kA AC and 36 kA DC as specified
Rated Ultimate Short-Circuit Breaking Capacity (Icu): Various values up to 65 kA AC and 36 kA DC as specified
Rated Uninterrupted Current (Iu): 160 A
Rated Voltage (Ur): 690 V
Recommended Screw Driver: Main Circuit M6
Release: TMD
Release Type: TM
Setting Range: 87.5…125 A
Short-Circuit Performance Level: N
Standards: IEC60947-2
Sub-type: XT1
Terminal Connection Type: Front
Terminal Type: Bolt
Tightening Torque: 6 N·m